期刊文献+

液体除湿空调系统的研究分析 被引量:2

Analysis of Liquid Desiccant Air Conditioning System
下载PDF
导出
摘要 在液体除湿过程中,空气与溶液之间发生的传热、传质作用是相互影响的,空气中的水蒸气分压力与溶液表面上的饱和蒸气压力差为两者之间的传质作用提供动力。由于除湿溶液喷淋在填料表面的同时,能够对流经填料之间的空气起到除尘过滤的作用,从而降低了空气中颗粒物的浓度,提高了进入室内空气的品质。但因空气和除湿溶液在填料表面直接接触进行传热传质,容易发生除湿空气夹带液体进入室内,因此对除湿空调系统做了湿式除尘以及泡沫夹带进行相关理论分析。 In the process of liquid dehumidification,heat transfer and mass transfer between air and solution are influenced mutually. Water vapor partial pressure in the air and the saturated vapor pressure difference on the surface of the solution provides the driving force for the mass transfer between the air and solution. The desiccant solution has the effect of dust removal filter to the air between packing,while it is sprayed on the surface of the packing,and the concentration reduction of particulate matter in air,raising the indoor air quality. But for the air and dehumidification solution,the heat and mass transfer on the filler surface directly,which is prone to dehumidification air with liquid entraining into the room,therefore the wet dust removal and foam entrainment for desiccant air conditioning system are analyzed theoretically.
出处 《建筑节能》 CAS 2017年第3期40-43,共4页 BUILDING ENERGY EFFICIENCY
关键词 液体除湿 蒸压差 湿式除尘 泡沫夹带 liquid desiccant steam pressure difference wet dust removal foam entrainment
  • 相关文献

参考文献3

二级参考文献22

  • 1赵云,施明恒.太阳能液体除湿空调系统中除湿剂的选择[J].工程热物理学报,2001,22(S1):165-168. 被引量:26
  • 2刘晓华,李震,江亿.溶液全热回收装置与热泵系统结合的新风机组[J].暖通空调,2004,34(11):98-102. 被引量:39
  • 3陈沛霖.蒸发冷却技术在非干燥地区的应用[J].暖通空调,1995,25(4):3-8. 被引量:46
  • 4Kessling W, Laevemann E, Peltzer M. Energy storage in open cycle liquid desiccant cooling systems [J]. Int J Refrig, 1998, 21(2):150-156.
  • 5中华人民共和国国家标准化管理委员会.GB 19576-2004 单元式空气调节机能源效率限定值及能效等级[S].北京:中国标准出版社,2004.
  • 6X H Liu,K Y Qu,Y Jiang.Empirical correlations to predict the performance of the dehumidifier using liquid desiccant in heat and mass transfer[J].Renewable Energy,2006,31:1627-1639.
  • 7C G Moon,P K Bansal,Sanjeev Jain.New mass transfer performance data of a cross-flow liquid desiccant dehumidification system[J].International journal of refrigeration,2009,32:524-533.
  • 8Fumo,Nelson,Goswami.Study of an aqueous lithium chloride desiccant system:air dehumidification and desiccant regeneration[J].Solar Energy,2002,22(4):351-361.
  • 9Chung T W,Ghosh T K,Hines A L.Comparison between random and structured packings for dehumidification of air by lithium chloride solutions in a packed column and theirheat and mass transfer correlations[J].Int Eng Chem Res,1996,35(1):192-208.
  • 10Chen L C,Kuo C L,Shyu R J.The performance of a packed bed dehumidifier for solar liquid desiccant systems[C] //Annual solar energy conference,1989:371-377.

共引文献31

同被引文献9

引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部