期刊文献+

改建美术馆空调通风系统的设计实践与问题分析 被引量:3

Design practice and problem analysis of air conditioning and ventilation system in art museum reconstruction
下载PDF
导出
摘要 介绍了民生现代美术馆改造工程的设计思路,通过现场测试,分析了室内环境参数对于不同人群热感觉的影响,建议控制展厅内的温度在24~26℃,各展厅之间的温度变化小于2℃比较合理。针对3层展厅夏季室内温度过高的问题,分析了产生问题的原因,并给出了解决方案。根据室内精装修的要求,提出了针对性的空调通风系统设计方案。 Presents the design idea of Minsheng Art Museum reconstruction project. Based on the field test. analyses the influence of indoor environment parameters on the thermal sensation of different people. Suggests that the temperature controlled in the exhibition hall is more appropriate between 24 to 26 ℃, and the temperature difference between the exhibition halls less than 2℃. Analyses the couses of the high indoor temperature in the third floor exhibition hall, and gives the solution. According to the requirements of the indoor decoration scheme, puts forward the design scheme of the air conditioning and ventilation system.
出处 《暖通空调》 北大核心 2017年第3期79-84,共6页 Heating Ventilating & Air Conditioning
关键词 美术馆 空调系统 中庭 精装修 测试 art museum, air conditioning system, atrium, decoration, test