基于部分行程测试法的在役电动阀设计与改造 被引量:3

The Design and Modification of the Electric Valve in Service Based on the Method of Partial Stroke Testing
下载PDF
导出
摘要 天然气输气站场安全完整性等级(SIL等级)受限于执行器。基于功能安全理论,对分输出站电动阀,将ESD全开全关动作测试改成部分行程测试,为实现其功能做以下改造:阀门电动执行机构内增加比例控制器,将其改造成可以控制开度的阀门;安装一个机械设备去限制阀门的开度,用专门的钥匙开关将机械限制设备的销子处于设定位置;增加在线检测和故障诊断通信,通过可视的故障诊断报警确保ESD阀门的有效性。 The safety integrity level(SIL level) of a gas pipeline station is limited to the actuator. Based on the theory of functional safety, electric valves in a gas distributing station will replace an ESD full open/closed action test with a partial stroke test. And to achieve its function we do the following transformation : an electric actuator installs a proportional controller, with which can control the open degree of the valve; a mechanical device, which can set mechanical limit pins to the setting position using a special key switch, can limit the degree of the valve; by way of the online detection and fault diagnosis of communication, the visual troubleshooting alarm can ensure the effectiveness of ESD valves.
作者 管文涌
出处 《仪器仪表标准化与计量》 2017年第1期32-36,共5页 Instrument Standardization & Metrology
关键词 功能安全 部分行程测试 比例控制器 机械限制 可视的故障诊断报警 Functional Safety Partial Stroke Testing Proportional Controller Mechanical Restriction Visual Troubleshooting Alarm
  • 相关文献

参考文献8

二级参考文献12

  • 1Goble,W.M.High Availability Systems for Safety and PerforrnancE-The Coverage Factor
  • 2Harris,D.E.Built-in Test for Fail-Safe Design.1986 Proceedings of the Annual Reliability and Maintainability Symposium,New York:IEEE,1986
  • 3Wmiam M.Goble.Safety assessment of control system and reliability
  • 4[1]Application of Safety Instrumented Systems for the Process Industries Research Triangle Park[Z].[S.1.]:[s.n.],1996.
  • 5[2]International Electrotechnical Commission.Functional safety of electrical/electronic/programmable electronic safety related systems[M].Geneva:Switzerland,1999.
  • 6[3]Frederick E B.Standard handbook of petroleum natural gas engineering[K].Houston:Gulf Publishing Company,1996.
  • 7刘民治 钟明勋.失效分析的思路与诊断[M].北京:机械工业出版社,1993..
  • 8古列维奇等著,肖隆水译,核动力装置用的阀门[M].北京:原子能出版社,1988.
  • 9GB/T20438.6—2010,电气/电子/可编程电子安全相关系统的功能安全第六部分:GB/T20438.2和GB/T20438.3的应用指南.
  • 10ISA-TR84.00.03-2002, Guidance for Testing of Process Sector Safety Instrumented Functions(SIF) Implemented as or Within Safety Instrumented Systems(SIS).

共引文献42

同被引文献38

引证文献3

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部