Mal-defrosting is a typical and undesirable operating phenomenon for air source heat pump(ASHP)in the heating operation.This paper introduces two types of the novel efficient defrosting control methods.One is the direct measurement method by applying tube encircled photoelectric sensor(TEPS),the other is the indirect measurement method by using the temperature-humidity-time parameter(THT).The accuracy and efficiency of two methods are verified by the field test.The test results indicate that the ASHP unit can be reasonable defrosting by using the TEPS method and the THT method,the average COP is increased by 10% and 12% respectively compared by using the traditional temperature-time(TT)method.The TEPS method and the THT method are competitive defrosting control methods that can be used for ASHP in practical application.