同塔四回线路纵向故障对零序方向保护的影响研究 被引量:6

Influence research of longitudinal fault on zero sequence direction protection for four parallel transmission lines on the same tower
下载PDF
导出
摘要 结合同塔四回输电线路的结构特点,针对同一电压等级的有电气联系和无电气联系的同塔四回线路,研究分析了同塔四回线路发生单回线纵向故障时线间互感对零序方向保护的影响,利用网络拓扑的等效变换,计算出了各回线路上零序电压、零序电流的幅值和相角特征。分析表明同塔四回线路单回线路纵向故障时,对于两侧均无电气联系的同塔线路,零序方向保护存在误动的风险,对于两侧均有电气联系的线路,零序方向不会误动。最后通过PSCAD建立同塔四回线路的模型,对单相断线纵向故障进行了仿真,仿真结果验证了理论分析的正确性。 Based on the structural characteristics of the four circuit transmission lines on the same tower and the lines with/without electrical connection on the same voltage level, this paper analyzes the influence of the mutual inductance between the lines on zero-sequence directional protection when single line longitudinal fault occurs on four circuit transmission lines on the same tower, and calculates the amplitude and phase angle characteristics of zero sequence voltage and current on each line by using the equivalent transformation of the network topology. The analysis indicates that when the single line longitudinal fault occurs on four circuits on the same tower, there is a risk of real-operation of zero sequence directional protection for the line without electrical connection on both sides; for the line with electrical connection on both sides, the zero sequence direction will not real trip. Finally through the PSCAD, the model of four circuits on the same tower is established and the single-phase line break is simulated. Simulation results verify the correctness of the theoretical analysis.
机构地区 许继集团
出处 《电力系统保护与控制》 EI CSCD 北大核心 2017年第7期114-120,共7页 Power System Protection and Control
基金 国家电网公司科技项目(521702150007):"同塔多回输电线路纵向故障保护防误动研究"
关键词 零序互感 同塔四回输电线路 纵向故障 零序方向元件 zero-sequence mutual induction four-circuit transmission lines on the same tower longitudinal fault zero sequence power directional component
  • 相关文献

参考文献15

二级参考文献128

共引文献211

同被引文献93

引证文献6

二级引证文献33

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部