期刊文献+

直埋热水供热管道保温层合理厚度计算 被引量:1

Calculation of Reasonable Thickness of Insulation Layer for Directly Buried Hot-water Heating Pipeline
下载PDF
导出
摘要 结合工程实例,对DN 1 400 mm直埋热水供热管道(供回水管)合理厚度的计算方法进行探讨。在计算供热管道保温层合理厚度时,既要满足相关标准规范对保温层外表面温度<50℃的要求,又要满足敷设区域地表下1 m以上范围内任意点土壤温度≤30℃的不影响绿化带植物的生长要求以及确保管网的热损失率小于或等于2%的限定条件。 The calculation method of reasonable thickness of DN 1 400 mm directly buried hot-water heating pipeline which is supply and return water pipeline is discussed combined with an engineering exam- ple. When the reasonable thickness of the insulation layer of heating pipeline is calculated, the following requirements should be met including that the outer sur- face temperature of the insulation layer should be less than 50 ~C, the soil temperature should be less than or equal to 30℃ at any point in the range of more than i m below to insure that the surface in the laying area does not affect the growth of plants in the green belt, and the heat loss rate of heat-supply network should be less than or equal to 2%.
作者 贺璠 马斌 郑萌 HE Fan MA Bin ZHENG Meng
出处 《煤气与热力》 2017年第4期24-26,30,共4页 Gas & Heat
关键词 直埋热水供热管道 保温层 合理厚度 directly buried hot-water heating pipeline insulation layer reasonable thickness
  • 相关文献

参考文献2

二级参考文献7

  • 1杨良仲,张连钢,曹宝军,徐善忠.大管径热水直埋供热管道保温层厚度的计算[J].煤气与热力,2007,27(2):70-72. 被引量:17
  • 2GB/T 4272-1992,设备及管道保温技术通则[S].
  • 3GB 8175—87,设备及管道保温设计导则[S].
  • 4[苏]约宁AA(著),单文昌,尚雷(译).供热学[M].北京:中国建筑工业出版社,1986.
  • 5章锡民,任泽霈,梅飞鸣,等.传热学(第4版),[M].北京:中国建筑工业出版社,2001.
  • 6范季贤,汤惠芬.热能工程设计手册[M].北京:机械工业出版社,1999.
  • 7GB8175-87,设备及管道保温设计导则[S].