摘要 结合大中型火力发电厂集中空调系统设计,发现传统的气流组织方式并不是满足工艺设备温湿度要求和人员舒适性的最佳气流组织方式。从室内环境温湿度、洁净度、人员舒适性、室内装饰装修、电缆走线等方面研究了在电厂集控室、电子设备间等采用孔板上送下回方式的可行性。结合某实际工程案例进行孔板送风的室内布置,采用Airpak软件对该案例室内环境进行了数值模拟,直观表征了室内温度场和流场等。 Combined with central air conditioning system design of large and middle scales of fossil- fuel power plants, finds that the traditional air distribution is not the best way to meet the requirements of temperature and humidity of process equipment and occupants' comfort. Studies and discusses the feasibility of perforated ceiling air supply system application to control room and electronic equipment room from indoor temperature, humidity, cleanliness, comfort, interior decoration and cable routing. Taking a project as an example, adopts perforated ceiling air supply system and simulates the indoor environment using Airpak software to represent the indoor temperature and flow field visually.
出处 《暖通空调》 北大核心 2017年第4期113-117,共5页 Heating Ventilating & Air Conditioning
关键词 火力发电厂 集中空调系统 气流组织 孔板送风 数值模拟 fossil-fuel power plant, central air conditioning system, air distribution, perforated ceilingair supply, numerical simulation
  • 相关文献

参考文献2

二级参考文献11

  • 1北京建筑设计研究院.现代办公楼设计[M].北京:中国建筑工业出版社,1995..
  • 2丛惠珠.色彩标志信号[M].北京:化学工业出版社,2001..
  • 3庄惟敏.建筑策划导论[M].北京:中国水利水电出版社,2001..
  • 4.DGJ08-83-2000.防静电工程技术规程[S].,2000..
  • 5Nielsen P V. Description of supply openings in numerical models for room air distribution [J]. ASHRAE Transactions, 1992, 98(1): 963-971.
  • 6Li Z H, Zhang J S, Zhivov A M, et al. Characteristics of diffuser air jets and airflow in the occupied regions of mechanically ventilated rooms-a literature review [J]. ASHRAE Transaction, 1993, 99(2): 1119-1120.
  • 7CHEN Q Y, Moser A. Simulation of a multiple-nozzle diffuser [A]. Proceedings of the 12th AIVC Conference on Air Movement and Ventilation Control within Buildings [C]. Ottawa: The IEA Air Infiltration and Ventilation Centre, 1991.
  • 8魏学孟,张奕昌.矢流洁净工作台数值模拟[J].暖通空调,2000,30(5):72-74. 被引量:3
  • 9赵彬,李先庭,彦启森.室内空气流动数值模拟的风口模型综述[J].暖通空调,2000,30(5):33-37. 被引量:64
  • 10周天泰,陈志洁,刘继平.香港某医院手术室内通风效果的数值研究[J].暖通空调,2001,31(5):13-14. 被引量:2