期刊文献+

某燃气机组旁路控制异常分析与处理

Abnormity Analysis and Processing of Bypass Control System in a Gas-Steam Combined Cycle Unit
下载PDF
导出
摘要 某燃气机组在停机过程中经常出现中旁压力控制品质恶化现象,通过对中旁压力控制异常原因分析,发现由于逻辑设计存在漏洞,导致机组停机过程中中旁调阀的控制模式转换不及时,调阀开启过慢,引起中旁压力高异常。通过对控制参数的修改初步解决了该问题,对于进一步优化亦提出建议方案。 A gas-steam generator often appears bypass pressure control quality deterioration during shut-down period. Based on the analysis of pressure anomaly, it's found that the control mode of adjusting valve switching not in time caused by the loopholes in the logical design. Because the adjusting valve opens slowly, the pressure of bypass system in intermediate pressure cylinder appears high value anomaly. Through to modify the control parameters, the problem has been resolved provisionally. This paper also puts forward the proposals for further optimization.
作者 江溢洋
出处 《安徽电气工程职业技术学院学报》 2017年第1期66-70,共5页 Journal of Anhui Electrical Engineering Professional Technique College
关键词 中旁压力 中旁调门 控制逻辑优化 bypass system pressure bypass system adjusting valve control logic optimization
  • 相关文献

二级参考文献14

共引文献24

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部