宜宾±800kV换流站接地极线路断线故障分析 被引量:1

Research and Analysis of Electrode Line Breakage Fault of Yibin ±800kV Converter Station
下载PDF
导出
摘要 介绍了宾金直流输电线路金华换流站极Ⅱ±800 k V直流穿墙套管发生故障后,接地极线路断线故障过程。采用EMTP-ATP软件对故障前后系统电流为5 970 A和5 215 A时接地极导线和避雷线分流情况进行了仿真计算,并与录波图进行了比较。根据计算结果分析了绝缘子掉串及导线断线原因,以及避雷线熔断原因。提出了接地极线路绝缘配置建议。 Alter fault occurred on +800 kV DC wall bushing of pole II in Jinhua converter station, the grounding line also has breakage fault. By using ATP-EMTP, response of grounding electrode conductor and shielding wire is sinmlated with 5 970 A and 5 215 A fauh current. The results are compared with recorded fault waveform. According to calculation results, the breakage reasons of insulator string and shielding wire are analyzed in detail. The recommended grounding line insulation configuration is also intrudueed.
出处 《中国电力》 CSCD 北大核心 2017年第4期77-80,86,共5页 Electric Power
关键词 ±800 KV 接地极 导线 避雷线 断线故障 +800 kV earth electrode power conductor shielding wire transmission line breakage fault