摘要
针对某新建110k V变电站启动调试过程中电容器柜内电抗器噪声严重超标问题,经过分析和测试,将其电抗率由1%提高到5%,谐振被遏制,噪声也大幅度下降。文章通过理论分析与计算,验证了该改造的合理性。最后总结了串联电抗器电抗率选取的一般原则,并提出了处理建议。
For the serious noise overweight problem of reactor during the startup debugging process of a newly built 110kV substation, the reactance ratio of the series reactor is turned from 1% up to 5 % after analysis and test, which restrains the resonance and sharply reduce the noise. This paper proves the rationality of the alteration project through theoretical analysis and calculation. Based on this conclusion, this paper summarizes the general principles of the reactance ratio selection and proposes some suggestions.
作者
杜欢
DU Huan(Kunneng Electrical Engineering Designing (Shanghai) Co., L td .,Shanghai 201103, China)
出处
《供用电》
2017年第5期60-63,共4页
Distribution & Utilization
关键词
并联电容器
串联电抗器
噪声分析
电抗率
谐振
shunt capacitor
series reactor
noise analysis
reactance ratio
resonance.