摘要
供电网公共连接点处主谐波源的定位,是对谐波污染采取合理抑制措施的重要前提。从非正弦条件下功率的分解方法出发,提出一种基于谐波畸变功率的主谐波源定位新方法,实现了适用于IEEE Std.1459-2010标准的主谐波源定位。通过比较同一系统供电线性与非线性负荷情况下视在功率分量与瞬时功率分量的对应关系,证明了谐波畸变功率对于主谐波源定位的有效性。多种情况下的仿真分析和实测验证结果证明了所提方法的正确性和合理性。
The positioning of harmonic sources on the point of common coupling (PCC) is the important premise of responsibility proration and harmonic elimination. In this paper, a novel method of the positioning of main harmonic sources based on harmonic distortion power is proposed, which is applicable for the IEEE Std. 1459-2010 standard. By comparing the corresponding relationship between the instantaneous power components and apparent power compo- nents of linear and nonlinear load cases, the effectiveness of the proposed method is proved. Several cases of simula- tion analysis and measurement results prove the validity and rationality of this method.
出处
《电测与仪表》
北大核心
2017年第9期71-77,共7页
Electrical Measurement & Instrumentation
基金
国家电网公司总部科技项目"电能质量经济损失及节能效益评估关键技术研究"(SGRI-DL-71-15-006)
关键词
谐波源定位
畸变功率
功率定义
电能质量
positioning of harmonic sources, distortion power, power definitions, power quality