民用建筑室内新风量检测方法影响因素的研究 被引量:2

Investigation on the impact factors for measuring indoor fresh air ventilation rate in civil buildings
下载PDF
导出
摘要 新风对于稀释室内空气中的有害物质、改善室内环境有着重要的意义。新风量则是衡量新风的有效手段,目前不设独立新风系统的建筑室内新风量测量广泛采用CO_2示踪气体法。本文通过一系列实验探讨CO_2初始浓度、门窗开关方式、室外风速以及室内杂物对室内新风量检测结果的影响。实验结果表明CO_2初始浓度、门窗开关方式、室外风速、室内杂物这些因素均对新风量检测值均存在不同程度的影响,其中室外风速和室内有无杂物对新风量检测结果的影响最为明显。 Fresh air is one of the most important factors which effectively dilute the indoor air harmful substances and improve the indoor air quality. In this paper, fresh air ventilation rate was used to evaluate fresh air, and CO2 was taken as the tracer gas to measure the fresh air ventilation rate, such method is widely used in non - mechanical ventilation buildings. The aim of this paper is to investigate the effects of CO2 initial concentration, the door/window switch mode, outdoor wind speed and indoor furniture on measuring indoor fresh air ventilation rate. It is found that CO2 initial concentration, the door/window switch mode, outdoor wind speed and indoor debris could all impact the measurement of fresh air ventilation rate, among of them, the outdoor wind speed and indoor furniture have the most obvious influence.
出处 《福建建设科技》 2017年第3期80-82,共3页 Fujian Construction Science & Technology
关键词 室内新风量 室内空气质量 CO2示踪气体法 fresh air ventilation rate indoor air quality tracer gas of CO2
  • 相关文献

参考文献4

二级参考文献16

  • 1何新星,王跃思,刘广仁,孙扬.北京大气CH_4、CO_2、TOC日变化规律及垂直分布的自动连续观测[J].中国环境监测,2005,21(3):62-66. 被引量:9
  • 2李晶,王跃思,刘强,王明星.北京市两种主要温室气体浓度的日变化[J].气候与环境研究,2006,11(1):49-56. 被引量:25
  • 3赵志安,单寄平.办公楼类型空调建筑物间歇空调设计负荷的简化计算法[M]∥空调负荷实用计算法.北京:中国建筑工业出版社,1989
  • 4Seppanen OA,Fisk WJ,Mendell MJ.Association of ventilation rates and CO2 concentrations with health and other responses in commercial and institutional buildings[J].Indoor Air,1999,9:226 - 252.
  • 5ECA (European collaborative action).Urban air,indoor environment and human exposure,ventilation,good indoor air quality and rational use of energy[R].2003.
  • 6Seppanen OA,Fisk WJ,Faulkner D.Cost benefit analysis of the night time-ventilative cooling in office building[C].Proceedings of Health Buildings,Singapore,2003,3.
  • 7Seppanen OA,Fisk WJ.Summary of human response to ventilation[J].Indoor Air,2004,14(7):102 - 118.
  • 8ASTM D 6245-98.Guide for using Carbon Dioxide Concentrations to Evaluate Indoor Air Quality and Ventilation[S].
  • 9GB/T 18204.18-2000 公共场所室内新风量测定方法[S].北京:中国标准出版社,2000.
  • 10ASTMD 5157-91.Standard Guide for Evaluation of Indoor Air Quality Models[S].

共引文献39

同被引文献9

引证文献2

二级引证文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部