期刊文献+

热湿工况下工位辐射空调的热舒适实验研究 被引量:8

Experimental analysis of thermal comfort in the hot-humid environment with radiant panel workstation
下载PDF
导出
摘要 为研究热湿工况下使用工位辐射空调的人体热舒适情况,在人工环境实验室内,通过改变环境背景温度来影响人体的热感觉,并采用热感觉投票(TSV)作为评价标准,重点研究了人体头部、躯干、上肢、下肢以及整体热感觉情况。实验结果表明,尽管背景环境参数超出舒适范围,但使用工位辐射空调能维持受试者的舒适状态,即背景温度稳定在28℃时,平均整体热感觉投票值低于+0.2;背景温度为30℃时,受试者热感觉仍能满足ASHRAE规范中规定的80%可接受范围要求。 This study focuses on thermal comfort of subjects with radiant panel workstation in hot-humid environment. The experiments are carried out in the experimental chamber. Thermal sensations of whole body, head, trunk, upper limb and lower limb of subjects are collected on the basis of seven-scale vote. The obtained results indicate that the average vote of thermal sensation at 28 ℃ is lower than +0. 2, and subjects could maintain comfortable condition well with radiant panel workstation (within the 80% acceptable range of ASHRAE Standard) although indoor environment is as high as 30 ℃. This study provides a new way for both extending comfortable temperature range and saving energy in buildings.
出处 《土木建筑与环境工程》 CSCD 北大核心 2017年第4期11-16,共6页 Journal of Civil,Architectural & Environment Engineering
基金 国家自然科学基金(51578220)~~
关键词 热感觉 热舒适 环境参数 工位空调 thermal sensation thermal comfort environmental parameter radiant panel workstation
  • 相关文献

参考文献4

二级参考文献41

  • 1李俊,孙淑凤,狄洪发,赵荣义.稳态条件下人体对个体送风的热反应研究[J].暖通空调,2004,34(12):1-6. 被引量:19
  • 2陈启,马一太.辐射顶板空调系统的优势[J].节能技术,2005,23(1):40-43. 被引量:29
  • 3张宇峰,赵荣义.局部热暴露对人体全身热反应的影响[J].暖通空调,2005,35(2):25-30. 被引量:11
  • 4杜芳莉.毛细管平面辐射空调系统节能技术[J].西安航空技术高等专科学校学报,2012,30(1):58-60. 被引量:1
  • 5王子介.地板辐射供暖与辐射供冷[M].北京:机械工业出版社,2004.
  • 6Bauman F S,Arens E.Task/ambient conditioning systems:engineering and application guidelines,No.4902510[R].Berkeley:University of California,1996.
  • 7Kaczmarczyk J,Melikov A,Fanger P O.Human response to personalized ventilation and mixing ventilation[J].Indoor Air,2004,14 (8):17-29.
  • 8Hayashi J,Lee S,Tomioka Y,et al.The Effect of isothermal task unit on thermal comfort[C].Coimbra,Portugal:Proceedings of the 9th International Conference on Air Distribution in Rooms,2004.
  • 9Amai H,Tanabe S,Akimoto T,et al.Thermal sensation and comfort with three task conditioning systems[C].Beijing:Tsinghua University Press,2005.
  • 10Zhang H.Human thermal sensation and comfort in transient and non-uniform thermal environments[D].Berkeley:University of California,2003.