小型数据中心机房布局及气流组织研究 被引量:13

Study on computer room layout and air distribution in small scale data center
下载PDF
导出
摘要 以实际项目的机房为例,通过CFD模拟的方法研究小型机房的合理布局形式,分析各形式下的温度和速度分布情况,利用热环境评价指标来评价冷却效果,并对刚投入使用的机房进行了实验测试。研究表明,敞开式冷热通道的两侧和顶部都存在冷热空气掺混现象,降低了冷空气的利用效率;在机房尺寸允许的情况下,空调送风方向应与冷热通道平行,布置机架时应尽量增加每排的机柜数量;当机房发热量较小时,冬季室外空气的自然冷量可以满足冷却要求;封闭冷通道的方式可以减少冷空气短路,提高冷却效率。 Taking actual computer room as an example,reasonable layout of small computer room was studied through CFD simulation method,temperature and velocity distribution in each layout was analyzed,and cooling effect was evaluated using thermal environment evaluation indices. And an experiment was carried out on the new computer room. The study shows that cold and hot air mix at the two sides and top of the open cold and hot aisles,which reduces the utilization of cold air. In the case of computer room's size allows,the air supplying direction of air conditioning should be parallel with the direction of the cold and hot aisles,and the number of racks in each row should be increased as much as possible. When the heat quantity of the computer room is small,the natural cooling capacity of outdoor air in winter can meet the cooling requirement. Enclosing the cold aisle can reduce the short circuit of cold air and improve the cooling efficiency.
出处 《低温工程》 CSCD 北大核心 2017年第3期61-68,共8页 Cryogenics
基金 浙江省低碳建筑能源环境工程技术研究中心资助项目(编号:2011E10033)
关键词 小型数据中心 机房布局 气流组织 模拟 实验 small scale data center computer room layout air distribution simulation experiment
  • 相关文献

参考文献3

二级参考文献25

  • 1王金.3G网络拒绝重复建设[N].通信产业报,2006-04-20.
  • 2R. Sharma, C. Bash, C. Patel, M. Beitelmal, Experimental investigation of design and performance of data centers, in: Themlomechanical Phenomena in Electronic Systems - Proceedings of the Intersociety Conference- Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, 2004, vol. 1, pp. 579- 585.
  • 3A. Shah, V. Carey, C. Bash, C. Patel, Energy analysis of data center thermal management systems, J. Heat Transfer, 2008, in press.
  • 4A. Shah, V. Carey, C. Bash, C. Patel, An energy- based figure of merit for electronic packages, J. Electron. Packag 128 (4) (2006)360- 369.
  • 5C.D. Patel, R. Shamla, C.E. Bash,A. Beitelmal, Thermal considerations in cooling large scale high compute density data centers, in: Proceedings of 2002 Inter Society Conference on Thermal Phenomena, 2002.
  • 6S. Kang, R.R. Schmidt, K.M. Kelkar, A. Radmehr, S.V. Patankar, A methodology for the design of perforated tiles in raised floor data centers using computational flow analysis, IEEE Transactions on Computer and Packaging Technologies 24 (2) (2001) 177- 183.
  • 7K. Karki, S. Patankar, A. Radmehr, Techniques for controlling airflow distribution in raised - floor data centers, Adv. Electron. Packag. 2 (2003) 621- 628.
  • 8R. Schmidt, E. Cruz, Cluster of high powered racks within a raised floor computer data center: effect of perforated tile flow distribution on rack inlet air temperatures, J. Electron. Packag., Trans. ASME, Therm. Manag. Electron. Syst. : Four Decades of Progress, December 126(4) (2004)510-518.
  • 9S. Shrivastava, B. Sammakia. R. Schmidt, M. Iyengar, Comparative analysis of different data center airflow management configurations, in: Proceedings of the International Electronic Packaging Technical Conference and Exhibition, San Francisco, CA, 2005.
  • 10K. Karki, S. Patankar, Airflow distribution through perforated tiles in raised - floor data centers, Build. Environ. 41 (2006) 734 - 744.

共引文献83

同被引文献96

引证文献13

二级引证文献46

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部