期刊文献+

基于发电机机端和中性点零序电压值的故障类型判断 被引量:1

Generator Failures Identification Based on Motor Terminal and Neutral Zero Sequence Voltage
下载PDF
导出
摘要 发电机发生故障后,快速且准确的故障诊断方法有利于排除故障和缩短停机时间。发电机出现TV断线或定子接地故障时,通过分析发电机机端电压、机端零序电压、中性点零序电压数值的升高或者降低进行故障定位,确定发电机一次回路或者二次回路的故障类型及大致范围,又进一步根据现场经验指出具体的故障点,此方法只需对比故障前后发电机的电压值,简单易行。 When generator aborts,finding accurate solutions to generator failures can help with troubleshooting and shortening halt period. When generator failures such as TV disconnection or stator ground fault happen,through analyzing fluctuation of motor terminal voltage,motor terminal voltage and neutral zero sequence voltage,it can narrow down the type and scope of generator failures in primary circuit and secondary circuit. And then it can find out specific generator failures. This simple method is conducted by comparing the generator voltage before and after the machine breakdown. It is worth widely recommended.
出处 《湖南电力》 2017年第3期62-64,67,共4页 Hunan Electric Power
关键词 发电机 机端电压 中性点零序电压 故障判断 generator motor terminal voltage neutral zero sequence voltage accident identification
  • 相关文献

参考文献6

二级参考文献32

  • 1邰能灵,邓妍.基于小波启动的故障分量相角比差发电机定子接地保护[J].电力系统自动化,2004,18(13):60-63. 被引量:4
  • 2邰能灵,吴宏晓.基于小波变换的选择性发电机100%定子单相接地保护方案[J].中国电机工程学报,2004,24(11):12-16. 被引量:13
  • 3毕大强,王祥珩,李德佳,余高旺,王维俭.发电机定子绕组单相接地故障的定位方法[J].电力系统自动化,2004,28(22):55-57. 被引量:39
  • 4王启龙(Wang Qilong).火电厂汽轮发电机组故障诊断系统的研究与开发:[硕士学位论文](Research and Develop of the Fault Diagnosis System for Thermo Power Plant Steam Turbine Units,Thesis)[M].南京: 东南大学 (Nanjing: Southeast University),2000..
  • 5虞和济(Yu Heji).基于神经网络的智能诊断(The Intelligent Diagnosis Based on Neural Network)[M].北京:冶金工业出版社(Beijing: Metallurgy Industry Press),2000..
  • 6贺家李;宋从矩.电力系统继电保护原理[M]天津:天津大学出版社,2004.
  • 7TAI N L, STENZEL J. Differential protection based on zero- sequence voltages for generator stator ground fault I-J~. IEEE Trans on Power Delivery, 2007, 22(1): 116-121.
  • 8王峰.国产300Mw发电机封母受潮的影响及查找分析[J].中国电业,2013(3):70-72.
  • 9吕景顺,孙亚明,马建海,等.发电机出口电压互感器匝间故障引起机组定子接地保护动作实例分析[C]//2009年中国电机工程学会年会,2009年11月25-27日,天津:1-3.
  • 10张琦雪,陈佳胜,陈俊,严伟,沈全荣.大型发电机注入式定子接地保护判据的改进[J].电力系统自动化,2008,32(3):66-69. 被引量:32

共引文献68