期刊文献+

小电流接地故障无功功率分析及选线新方法 被引量:41

Reactive power analysis and novel faulty selection method in resonant grounding system
下载PDF
导出
摘要 对于谐振接地系统的单相接地故障,由于现场普遍存在电压互感器(PT)和电流互感器(CT)极性反接的现象,当仅仅利用故障的暂态无功功率方向进行选线时极易发生误选。分析了PT、CT极性反接对故障暂态和工频无功功率的影响,提出一种利用故障的工频无功功率对暂态无功功率进行修正再选线的新方法。即:修正后的暂态无功功率为负值的线路为故障线路,如果所有出线修正后的暂态无功功率都是正值则为母线接地。该方法可以忽略PT和CT的极性反接影响,扩大了选线适用范围。仿真和现场的数据证明了该方法的可行性。 Because of the incorrect polarity connection of voltage transformer and current transformer in field, faulty feeder selection based on transient reactive power direction leads to wrong easily when there is a single-phase earth fault in resonant grounding system. In this paper, the effect of the incorrect polarity connection of voltage transformer and current transformer on transient reactive power and power-frequency reactive power is analyzed. A novel method using the power-frequency reactive power to correct the transient reactive power for faulty feeder selection is proposed. The faulty feeder is the one which the corrected transient reactive power is negative. If all of the corrected transient reactive powers are positive, it is bus fault. The proposed method is independent of polarity connection of voltage transformer and current transformer, which enlarges the selection scope. The feasibility of the new method is verified by digital simulation and field fault data.
作者 潘本仁 宋华茂 张秋凤 熊华强 俞小勇 PAN Benren SONG Huamao ZHANG Qiufeng XIONG Huaqiang YU Xiaoyong(State Grid Jiangxi Electric Power Research Institute, Nanchang 330096, China College of Information and Control Engineering, China University of Petroleum (East China), Qingdao 266580, China Shengli Oilfield Shengli Power Machinery Group Co., Ltd., Dongying 257000, China Electric Power Research Institute, Guangxi Power Grid Corporation, Nanning 530023, China)
出处 《电力系统保护与控制》 EI CSCD 北大核心 2017年第14期51-56,共6页 Power System Protection and Control
基金 国家自然科学基金项目(51477184) 江西省电力公司科技项目(521820150014)~~
关键词 谐振接地系统 单相接地故障 故障选线 互感器极性反接 暂态无功功率方向 resonant grounding system single-phase earth fault faulty feeder selection incorrect polarity connection of transformer transient reactive power direction
  • 相关文献

参考文献16

二级参考文献159

共引文献605

同被引文献445

引证文献41

二级引证文献300

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部