期刊文献+

500kV电力变压器内部过热故障分析及处理 被引量:5

Analysis and Processing of Internal Overheat Fault of 500kV Transformer
下载PDF
导出
摘要 对某发电厂1台500 kV变压器进行油色谱试验时发现总烃和乙炔体积分数异常。通过停电、排油、滤油、拆附件、吊罩检查,发现过热放电痕迹,确定故障原因为漏磁场引起的漏电流在变压器油箱上、下沿的限位挡铁处放电。通过打磨超高的限位挡铁,增加油箱磁屏蔽和上下箱沿加装铝、铜排等方式,消除了变压器异常故障。 The total hydrocarbon and acetylene content in the oil chromatographic test of a 500 kV power plant transformer was abnormal.Through the power cut,oil extraction,oil filter,demolition annex and hanger inspection,maintainer found the overheating discharge traced at the scene,and determind the cause of the malfunction.The transformer anomaly can be eliminated by sanding the ultra-high block iron,increasing the magnetic shield of the fuel tank,and the top and bottom boxes,along the aluminum and copper lines.
出处 《内蒙古电力技术》 2017年第3期90-92,共3页 Inner Mongolia Electric Power
关键词 变压器 油色谱 过热 漏磁 总烃 乙炔 限位挡铁 transformer oil chromatogram overheating leakage magnetic total hydrocarbon acetylene block iron