期刊文献+

单芯XLPE电力电缆负载试验与铠装结构选型

Simulated load test of single core XLPE power cable and selection of armour construction
下载PDF
导出
摘要 通过非铠装、具有隔磁措施的钢丝铠装和全钢丝铠装单芯交联聚乙烯 (XL PE)绝缘电力电缆的模拟负载对比试验 ,证明单芯钢丝铠装电缆中的钢丝铠装结构 ,无论是否隔磁措施 ,都会产生大量的铠装损耗 ,大大降低电缆的载流量水平 ,严重时 ,可导致电缆热击穿。 Simulated load tests were conducted on single core XLPE power cables without armour, with wire armour with magnetic separation and with full wire armour. The result shows that the wire armour provided with magnetic separation or not may cause large armour loss. As a result, the current carrying capacity of the cable may be greatly reduced and the cable may breakdown in severe cases.
出处 《电线电缆》 北大核心 2002年第4期22-24,共3页 Wire & Cable
关键词 单芯XLPE电力电缆 负载试验 铠装结构 选型 single core XLPE power cables with wire armour current carrying capacity test selection of armour construction
  • 相关文献

参考文献1

二级参考文献2

  • 1李含荪.国产单芯海缆铠装结构的榷商.99中国电机工程学会变电专委会电力电缆分专委会年会“论文集”[M].,1999..
  • 2马国栋.电缆载流量试验研究报告[M].上海电缆研究所,2000..