阀冷系统24V电源缺陷引起的直流闭锁及策略优化

The cause analysis and strategy optimization of HVDC blocked by 24V power supply defects in the valve cooling system
下载PDF
导出
摘要 以±800 kV特高压直流阀冷系统的一次扰动误出口导致直流闭锁为切入点,详细分析了引起直流闭锁的原因,提出了阀冷系统传感器供电网络布局、传感器信号及控制逻辑的优化方案。该方案已在云广直流输电工程中实际运用,运用结果证明该套优化方案能够减少直流输电工程中因阀冷系统传感器故障而引起的闭锁事件。 In this paper, a disturbance ofe 800 kV Yun Guang UHVDC valve cooling system caused the UHVDC blocked as the break through point. And put forward the optimization scheme of valve cooling system in power supply network, sensor signal sensor layout and control logic. This scheme has been applied in Yun Guang HVDC project, the results prove that the optimized scheme can reduce the blocking events caused by sensor fault of valve cooling system.
作者 李德荣 LI Derong(Kunming Bureau, CSG EHV Transmission Company, Kunming 650217, China)
出处 《云南电力技术》 2017年第4期21-24,共4页 Yunnan Electric Power
关键词 高压直流 阀冷系统 传感器 电源布线 闭锁 HVDC Valve cooling system Sensor Power wire arranging Block
  • 相关文献

参考文献7

二级参考文献31

  • 1梁家豪,林睿,周翔胜.天广和贵广直流工程中的阀冷控制系统[J].高电压技术,2006,32(9):92-95. 被引量:19
  • 2Guizhou-Guangdong II Line ±500 kV DC Transmission Project--Valve Cooling System Maintenance Manual.
  • 3Guizhou -Guangdong II Line ±500 kV DC Transmission Project--Valve Cooling System Operating Manual.
  • 4Guizhou-Guangdong I Line ±500 kV DC Transmission Project--Valve Cooling System Maintenance Manual.
  • 5Tian-Guang HVDC transmission Project --Valve Cooling System Maintenance Manual.
  • 6中国南方电网超高压输电公司广州局换流站阀冷系统闭锁逻辑及其改进措施研究报告[R].广州:中国南方电网超高压输电公司广州局,2009.
  • 7中国南方电网超高压输电公司广州局.广州换流站运行规程[z].广州:中国南方电网超高压输电公司广州局,2004.
  • 8王兆安 黄俊.电力电子技术[M].北京:机械工业出版社,2004..
  • 9赵婉君.高压直流输电工程技术[M].北京:中国电力出版社,2004.
  • 10习超群,李辉,吴宁,等.银川东换流变电站运行规程.银川:国网运行分公司银川管理处,2010:63-67.

共引文献55

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部