摘要
针对目前强跟踪滤波器在电压暂态扰动检测方面,在强非线性系统下存在参数估计精度不够,高维滤波器模型下计算复杂等问题,结合STF和UKF提出一种基于改进的强跟踪无迹卡尔曼滤波器(MSTUKF)的电能质量扰动检测方法。在状态变量发生突变时,通过次优渐消因子自适应调节过程噪声协方差矩阵的权重,在满足强跟踪滤波器不同时刻残差序列正交条件下,推导MSTUKF成立的充分条件。该算法较传统的STF方法改善了滤波器的估计精度,无需求解雅可比矩阵,只需一次UT变换,计算复杂度降低,且保留了STF在模型失配情况下的强鲁棒性。将所提方法与传统STF进行对比,仿真实验结果表明:所提方法更能快速、准确地检测到电压暂降、暂态脉冲及暂态谐波信号发生的起止时刻,跟踪到突变幅值和突变相位,验证了改进的强跟踪UKF是电能质量扰动检测的一种好的解决方案。
Strong tracking filter has some problems in terms of power quality disturbances detection, such as inadequate accuracy in strong nonlinear system, calculation complexity in high dimensional filter model and poor filtering performance. This paper combines strong tracking filter with unscented Kalman filter and proposes a new method which is based on modified strong tracking Kalman filter(MSTUKF). When the sudden changes of the state variables occur, it derives the sufficient conditions for the establishment of the MSTUKF by the suboptimal fading factor which adaptively adjusts the weights of process noise covariance matrix on the condition that filter residual sequence is orthogonal at different time. The proposed method improves the filter estimation accuracy of the filter without calculating the Jacobian matrix when compared with the traditional STF method. Besides, it just needs one UT transformation. Therefore, the computational complexity is reduced, what's more, it retains the strong robustness of STF under model mismatch. Simulation results show that the proposed method is more rapid and has a higher accuracy detection of mutation starting and ending time of voltage sag, transient pulse and transient harmonic signal, tracking the mutation and mutant amplitude phase, which verifies the modified MSTUKF is a good solution for power quality disturbance detection.
出处
《电力系统保护与控制》
EI
CSCD
北大核心
2017年第19期109-116,共8页
Power System Protection and Control
基金
中国博士后科学基金资助项目(2015T80961)
重庆市自然科学基金项目(cstc2016jcyj A0214)~~
关键词
强跟踪
渐消因子
电能质量扰动
无迹卡尔曼滤波
strong tracking filter
fading factor
power quality disturbance
unscented Kalman filter