摘要
利用Fluent软件对不同形状车库内不同位置的变电所进行机械通风的温度场仿真,通过改变变电所位置和启动一定台数的排气扇进行散热情况研究,得出变电所的最佳位置。对某高校艺术会堂地下车库不同位置变电所的温度场进行仿真计算,搭建缩小比例的变电所模型并进行温度测试。对比测试温度与仿真温度,验证了地下车库变电所选址和散热方法的正确性。
In this article,we used Fluent to simulate the temperature fields of a distribution room at different locations in garages with different shapes. By change of its location and numbers of exhaust fans,the best place for the distribution room is located. We then make simulation of the temperature fields of a distribution room located differently at an underground garage in a university and the temperature field of it with reduced proportion. The results prove the effects of the location strategy and cooling methods for an underground garage.
出处
《厦门理工学院学报》
2017年第5期39-45,共7页
Journal of Xiamen University of Technology
基金
厦门理工学院高层次人才项目(YKJ15014R)
关键词
地下车库
变电所
选址
散热效果
Fluent模拟
温度场仿真
underground garage
distribution substation
location
cooling effect
fluent simulation
simulation of temperature field