摘要
针对差动保护各侧CT类型不一致可能会导致差动保护区外故障误动作的问题,文章通过安哥拉某新建电厂的发变组保护实例,进行差动保护整定计算和分析,得出选择P级和PX级CT构成差动保护,根据通用的整定计算原则,不会导致差动保护误动作的结论。
In order to solve the problem of differential protection possible to make differential protection calculation and analysis misoperation for the CT's inconsistent characteristics,it is through the example of a new power plant in Angola.It was concluded that, according to the general setting calculation principle,the selection of P-class and PX-class CT constitute differential protection will not lead to differential protection misoperation.
出处
《企业技术开发》
2017年第11期50-51,74,共3页
Technological Development of Enterprise
关键词
差动保护
整定计算
可靠性
PX级CT
P级CT
differential protection
relay setting
reliability
PX-class CT
P-class CT