摘要
为了检测35 kV干式空心电抗器运行中是否存在匝间绝缘缺陷隐患,本文利用PSCAD软件对干式空心电抗器采用高频脉冲振荡法进行仿真分析,并对某变电站6台干式空心电抗器进行匝间过电压试验,发现2台设备存在匝间绝缘缺陷,根据现场所测数据验证了仿真分析的可靠性。
In order to detect the inter-turn insulation defect of 35 kV dry-type air-core reactors m the operation, in this paper, the simulation analysis with high frequency pulse oscillation method for the air core reactor is made by the use of PSCAD software and inter--turn test for 6 units of dry type air-core reactors at certain substation is performed, finding two of them have the inter-turn insulation defect. And the simulation and analysis reliability is verified in accordance with the data measured at site.
作者
车传强
刘利强
王亚杰
吕超
王琼
CHE Chuanqiang;LIU Liqiang;WANG Yajie;LYU Chao;WANG Qiong(Inner Mongolia Electric Power Science & Research Institute, Hohhot 010020, China;College of Electric Power, Inner Mongolia University of Technology, Hohhot 010080, China)
出处
《电力电容器与无功补偿》
北大核心
2017年第6期75-79,共5页
Power Capacitor & Reactive Power Compensation
基金
内蒙古电力(集团)有限责任公司科技项目(20161067)
关键词
干式空心电抗器
匝间绝缘
高频脉冲振荡法
dry-type air-core reactor
inter-turn insulation
high-frequency pulse oscillation method