期刊文献+

基于ε-NTU方法的干湿联合冷却塔特性分析 被引量:4

Performance Analysis of Hybrid Cooling Tower Based on Effectiveness-NTU Method
原文传递
导出
摘要 本文基于ε-NTU方法建立了热力发电厂干湿联合冷却系统的热力计算模型,系统研究了干湿联合系统在降低机组夏季运行背压和出塔水温等方面的特性。在此基础上,结合我国部分城市气象数据,分析了干湿联合系统在多种气象环境下的适用性问题。结果表明:干湿联合系统可以有效改善空冷机组因夏季环境高温导致的背压升高、机组出力受限的问题,降低冷却塔出塔水温有助于提高发电厂的热经济性;干湿联合系统较适宜应用在低温低湿或者高温适湿的地区,在高温高湿地区则不建议采用。 Based on the effectiveness-NTU (ε-NTU) method, a mathematical model was set up for the hybrid (dry/wet) cooling system that is used in power plants. With this model, the characteristics of the hybrid cooling tower in adjusting outlet water temperature and influencing steam turbine back pressure were studied. Besides, the applicability of hybrid cooling system in different regions of China was analyzed with regional meteorological data. The results indicate that the hybrid cooling system helps to solve the problem of increased back pressure and reduced energy e^ciency of air-cooled power plants in summertime by effectively lowering the temperature of circulation cooling water. Generally the hybrid cooling system is appropriate to be applied in the areas with low temperature and low humidity, or high temperature and intermediate hmnidity. It is not fit for areas with high temperature and high humidity.
出处 《工程热物理学报》 EI CAS CSCD 北大核心 2018年第1期144-149,共6页 Journal of Engineering Thermophysics
基金 国家自然科学基金资助项目(No.51476055) 国家"973"计划资助项目(No.2015CB251503) 中央高校基本科研业务费专项资金资助项目(No.2016YQ03)
关键词 干湿联合冷却塔 ε-NTU法 计算模型 气象适用性 hybrid cooling tower effectiveness-NTU method modeling meteorological applicabil-ity
  • 相关文献

参考文献3

二级参考文献20

  • 1徐跃芹,屠珊,黄文江,李慧君.火电厂自然通风冷却塔性能研究[J].汽轮机技术,2005,47(5):357-359. 被引量:11
  • 2杨立军,杜小泽,杨勇平,刘登瀛.火电站直接空冷凝汽器性能考核评价方法[J].中国电机工程学报,2007,27(2):59-63. 被引量:72
  • 3史佑吉.冷却塔运行与试验[M].北京:水利电力出版社,..
  • 4钱焕群.盘管式储水桶传热过程理论研究及其系统经济优化分析.东南大学硕士学位论文[M].,1997.3.
  • 5DL/T933--2005,冷却塔淋水填料、除水器、喷溅装置性能试验方法[S].
  • 6高明,孙奉仲,史月涛,等.侧风环境下湿式冷却塔性能参数变化规律的试验研究[A].第二十一届全国水动力学研讨会暨第八届全国水动力学学术会议暨两岸船舶与海洋工程水动力学研讨会文集[c].2009.521-527.
  • 7Williamson N, Armfleld S, Behnia M. Numerical Simulation of Flow in a Natural Draft wet Cooling Tower - the Effect of Radial Thermo - fluid Fields [ J 1. Applied Thermal Enginering ,2008,28 (2 - 3 ) : 178 - 189.
  • 8Kranc SC. Performance of Counter - flow Cooling Towers with Structured Packings and Mal -distributed Water Flow[ J]. Numerical Heat Transfer, 1993,23 ( 1 ) : 115 - 127.
  • 9Smrekar J, Oman J, Sirok B. Improving the Efficiency of Natural Draft Cooling Towers [ J ]. Energy Conversion and Management,2006,47(9 -10):1086 -1100.
  • 10Kloppers J C,KrOger D G. Loss Coefficient Correlation forWetcooling Tower Fills[J]. Applied Thermal Engineering,2003,23 (17):2201 -2211.