期刊文献+

夏热冬冷地区超低能耗建筑热工优化设计及负荷分析 被引量:25

Thermal Design Optimization and Analysis on Load of Ultra-Low Energy Buildings in Hot Summer and Cold Winter Regions
原文传递
导出
摘要 超低能耗建筑已在全世界范围内得到推广,德国超低能耗技术体系较为完整,而我国夏热冬冷地区还未有根据气候条件及用能特征建立起的适应于夏热冬冷地区的气候适应型超低能耗建筑采暖供冷技术路线。本文对夏热冬冷地区超低能耗建筑围护结构的优化设计进行了研究探索,利用EnergyPlus进行建模分析,通过正交试验设计方法,研究外窗、外墙、屋面传热系数对建筑供热负荷、制冷负荷及全年总负荷的影响,得出最优围护结构设计方案。结果表明,在外窗传热系数为2.0 W/(m^2·K),外墙和屋面的传热系数为0.2 W/(m^2·K)时,全年总负荷最低。本文的研究结果可为夏热冬冷地区超低能耗建筑围护结构的设计提供借鉴,亦可为夏热冬冷地区超低能耗建筑采暖供冷技术路线提供基础。 Ultra-low energy buildings have been promoted worldwide. In the current study. Among others,Germany's ultra-low energy consumption technology system is relatively more complete. Yet,no climate-adaptive ultra-low energy building heating and cooling technology route has been planned for regions with hot summer and cold winter in China. In this paper,the optimal design of ultra-low energy building envelope in regions with hot summer and cold winter was studied. Using Energy Plus for modeling analysis and orthogonal test design method,the paper studies the influence of the heat transfer coefficient of the external window,external wall and roof on the heating load,the cooling load and the annual total load to obtain the optimal envelope design scheme. The study results showed that when the heat transfer coefficient of the external window was 2. 0 W/(m^2·K),the heat transfer coefficient of the external wall and the roof was 0. 2 W/(m^2·K) with the minimum total annual load. The results of the study will serve as the basis for the technical route planning of heating and cooling of ultra-low-energy consumption in regions with hot summer and cold winter.
机构地区 同济大学
出处 《建筑科学》 CSCD 北大核心 2017年第12期182-187,共6页 Building Science
基金 "十三五"国家重点研发计划项目"近零能耗建筑技术体系及关键技术开发"(21017YFC072600)
关键词 ENERGYPLUS 超低能耗建筑 模拟 正交试验 围护结构 EnergyPlus, ultra-low energy buildings, simulation, orthogonal test, enclosure structure
  • 相关文献

参考文献4

二级参考文献13

  • 1贾若芹,董奇英.节能建筑的百叶遮阳系统[J].建筑科学,2011,27(S2):101-103. 被引量:4
  • 2ANNICA M, NILSSON, JACOB C Jonsson. Light-scattering properties of a Venetian blind slat used for daylighting applications [J]. Solar Energy,2010,84 : 2103-2111.
  • 3PFROMMER P, LOMAS K J, KUPKE Chr. Solar radiation transport through slat-type blinds: A new model and its application for thermal simulation of buildings [J]. Solar Energy, 1996, 57(2) : 77-91.
  • 4ATHANASSIOS Tzempelikos, ANDREAS K Athienitis. The impact of shading design and control on building cooling and lighting demand [J]. Solar Energy, 2007, 81: 369-382.
  • 5李峥嵘,夏麟.基于能耗控制的建筑外百叶遮阳优化研究[J].暖通空调,2007,37(11):11-13. 被引量:9
  • 6A.J. Marszal,P. Heiselberg,J.S. Bourrelle,E. Musall,K. Voss,I. Sartori,A. Napolitano.Zero Energy Building – A review of definitions and calculation methodologies[J]. Energy & Buildings . 2011 (4)
  • 7Adamson,B.Passive Climatisation of Residential Buildings in China. Lun.2d University.Report TABK-92/3006 . 1992
  • 8Passive House Institute.Criteria for Certification of Passive Houses for Non-residential use[OL]. http://passiv.de/downloads/03_certification_criteria_nonresidential_en.pdf . 2014
  • 9张文字,王慧丽,徐强.上海居住建筑实际用能模式研究与应用[J].第一届夏热冬冷地区绿色建筑技术论坛论文集,2011:118-121.
  • 10邓天福,李景广,叶倩,张泉,叶剑军.外遮阳百叶隔热性能与采光分析[J].建筑热能通风空调,2008,27(4):13-18. 被引量:20

共引文献77

同被引文献211

引证文献25

二级引证文献82

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部