摘要 提出了采用交联聚乙烯在电缆本体上模注增强绝缘层的设计理念及方法。详细阐述了模注式接头的关键技术的相关原理和制作工艺,并通过导体接头电阻、绝缘层交联度、热延伸、绝缘交界面检查等手段验证其可靠性。根据此方法研制的110 kV模注式接头,已按照JB/T 11167.1—2011的检测标准通过型式试验,证明了设计理念的正确性。 The design concept and method of using XLPE to mold the reinforced insulation on the cable body are pro-posed. The related principle and fabrication process of the key technology of the extrusion molded joint are described in details. The reliability of joint is verified by means of conductor resistance, insulation degree, thermal extension tests and insulation interface inspection. Following this method, 110 kV extrusion molded joint was developed and passed the type tests, which verified the design concept.
出处 《电线电缆》 2018年第1期15-18,共4页 Wire & Cable
关键词 交联电缆 中间接头 模注式接头 型式试验 crosslinking cable intermediate joint extrusion molded joint type tests
  • 相关文献

参考文献4

二级参考文献20

  • 1吕亮,王霞,何华琴,付海金,屠德民.硅橡胶/三元乙丙橡胶界面上空间电荷的形成[J].中国电机工程学报,2007,27(15):106-109. 被引量:29
  • 2ELECTRA No. 171. 1997-CIGRE. Recommendations for mechan- ical tests on submarine cables [ S].
  • 3JB/T10181.1电缆载流量计算[S].
  • 4特乐斯特用于高压海底电缆生产的挤出技术[C]//中国电工技术学会电线电缆专委会2011年学术年会论文集.福州:2011.66.84.
  • 5CIGRE-21-02-ELECTRA-189-APRIL 2000 Recommendations for testing of long AC submarine cables with extruded insulation for system voltage above 30(36) to 150(170) kV[ S].
  • 6Mazzanti G, Marzinotto M. Extruded cables lbr high-voltage di- rect-current transmission: advances in research and development, chapter 5: improved design of HVDC extruded cable systems[M], 1st ed. New- Jersey, USA: John Wiley & Sons Incorporated, 2013: 209-256.
  • 7Ross R. Dealing with interface problems in polymer cable termina- tions[J]. IEEE Electrical Insulation Magazine, 1999, 14(4): 5-9:.
  • 8夏云杰,钟海杰,王锦明,等.交联聚乙烯绝缘电缆主体终端模注应力控制模块:中国,ZL.2013.20549923.3[P]l2014-03-05.
  • 9Rogti E Mekhaldi A, Laurent C. Space charge behavior at physical interfaces in cross-linked polyethylene under DC field[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2008, 15(5): 1478-1485.
  • 10Delpino S, Fabiani D, Montanari G C, et al. Polymeric HVDC cable design and space charge accumulation, part 2: insulation interfaces[J]. IEEE Electrical Insulation Magazine, 2008, 24(I): 14-22.

共引文献30

同被引文献47

引证文献5

二级引证文献18

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部