摘要 采用随机抽样的方法,对武汉某高校寝室、教室共50台空调机的过滤网和散热片进行涂抹采样,根据空调污染原理,采用《公共场所集中空调通风系统卫生规范》中微生物检测方法,检测其中的细菌数和真菌数。检测结果:过滤网上细菌均值为(1620.00)cfu/cm^2,真菌均值为(1286.68)cfu/cm^2;散热片上细菌均值为(1902.00)cfu/cm^2,真菌均值为(1612.32)cfu/cm^2,均超过国家空调卫生合格标准:细菌和真菌总菌落数均应≤100 cfu/cm^2。同时开展了网上问卷调查,了解广大师生对空调的使用和清洗情况,并针对反映的问题,给予相关建议和解决措施。 Using random sampling method to daubing samples of filter screens and heat sinks of 50 air-conditionings in dormitories and classrooms at Universities in Wuhan. According to the principle of air conditioner pollution, using the microbial detection methods of 《The central air-conditioning ventilation systems in public places health norms》to detect the number of bacteria and funguses on the filter screens and the heat sinks. The result display: the average quantity of bacteria on filter screens are(1620.00)cfu/cm^2,and the funguses of it are(1286.68)cfu/cm^2; the average quantity of bacteria on heat sinks are(1902.00)cfu/cm^2, and the funguses of it are(1612.32)cfu/cm^2, both of them have exceeded the National air conditioning hygiene standard: the total bacterial colonies of bacteria and funguses are not exceeding about 100 cfu/cm^2. Meantime, online questionnaire survey is carried out to understand the using and cleaning of air conditionings through teachers and students. And Provide relevant Suggestions and solutions to related problems.
机构地区 武昌理工学院
出处 《环境与发展》 2018年第1期161-162,共2页 Environment & Development
关键词 空调室内污染 危害 散热片 细菌和真菌总数 清洁情况 Indoor air pollution harm Heat sinks The number of bacteria and funguses Cleaning condition
  • 相关文献

参考文献4

二级参考文献13

共引文献77

同被引文献68

引证文献7

二级引证文献14

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部