期刊文献+

预应力预制混凝土剪力墙截面设计方法 被引量:10

Design method of prestressed precast concrete shear walls
原文传递
导出
摘要 预应力预制混凝土剪力墙通过后张拉高强无黏结预应力筋将分段预制墙板拼装成整体,剪力墙与基础连接处布置若干普通钢筋以增强墙体的耗能能力。预制剪力墙在侧向荷载作用接缝处张开,依靠重力荷载和无黏结预应力筋提供恢复力。参照现行规范和已有的试验结果,给出了预应力预制剪力墙的性能目标,提出了预应力预制剪力墙截面设计方法,包括剪力墙截面尺寸、预应力筋、耗能钢筋以及墙脚约束混凝土设计。以4层预应力预制框架剪力墙结构为算例,采用有限元分析软件Open SEES建立数值分析模型,结果表明本设计方法可满足预期目标,进而验证了设计方法的合理性。 Prestressd precast concrete walls are constructed by utilizing high-strength unbonded prestressed tendons,with mild steel reinforcements across the base-to-foundation joint designed to yield in tension to increase energy dissipation ability. Lateral displacements result in a gap opening at the wall-foundation connection,and gravity loading and prestressed tendons provide the restoring force. The paper introduces performance levels for prestressed precast shear walls that conform to current codes and test results. Section design procedure of precast shear walls is provided,including geometry of shear wall section,post tensioned tendons,mild reinforcement and confined concrete design. A4-story design example demonstrating a step-by-step application of the design procedure is also presented. The design approach is critically evaluated based on nonlinear static analysis by using Open SEES software. It is shown that the designed structure satisfies the design prerequisites set forth.
作者 杨博雅 吕西林 YANG Boya;LU Xilin(State Key Laboratory of Disaster Reduction in Civil Engineering, Tongji University, Shanghai 200092, Chin)
出处 《建筑结构学报》 EI CAS CSCD 北大核心 2018年第2期79-87,共9页 Journal of Building Structures
基金 国家自然科学基金项目(51638012)
关键词 预应力预制混凝土剪力墙 无黏结后张拉 自复位 设计方法 prestressed precast concrete shear wall unbonded post-tensioning self-centering design method
  • 相关文献

参考文献4

二级参考文献88

  • 1周剑,赵作周,侯建群,任宝双,初明进,刘继良.预制混凝土空心模剪力墙上下层插筋连接抗震性能试验研究[J].建筑结构学报,2015,36(6):44-52. 被引量:16
  • 2JGJ101-1996,建筑抗震试验方法规程[S].北京:中国建筑工业出版社,1997
  • 3FEMA 273 NEHRP guidelines and commentary for seismic rehabilitation of buildings [ S ]. Washington DC, USA: Federal Emergency Management Agency, 1997.
  • 4FEMA 356 Prestandard and commentary for the seismic rehabilitation of buildings[ S]. Washington DC, USA: Federal Emergency Management Agency, 2000.
  • 5FEMA 445 Next-generation performance-based seismic design guidelines: program plan for new and existing buildings [ S]. Washington DC, USA : Federal Emergency Management Agency, 2007.
  • 6Report of the seventh joint planning meeting of NEES/ E-defense collaborative research on earthquake engineering[ R]. PEER 2010/109. Berkeley: University of California, Berkeley, 2010.
  • 7Roh H. Seismic behavior of structures using rocking columns and viscous dampers [ D ]. Buffalo : University at Buffalo, The State University of New York. Department of Civil, Structural and Environmental Engineering, 2007.
  • 8Housner G W. The behavior of inverted pendulum structures during earthquakes [ J ]. Bulletin of the Seismological Society of America, 1963, 53 (2) : 403- 417.
  • 9Hukelbridge A A, Clough R W. Preliminary experimental study of seismic uplift of a steel frame [ R ]. Report No. UCB/EERC-77/22. Berkely: University of California, Berkely, 1977.
  • 10Hukelbridge A A. Earthquake simulation tests of a nine story steel frame with columns allowed to uplift [ R ]. Report No. UCB/EERC-77/23. Berkely: University of California, Berkely, 1977.

共引文献449

同被引文献56

引证文献10

二级引证文献39

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部