期刊文献+

电网畸变条件下有源电力滤波器同步锁相研究 被引量:2

Synchronous Reference Frame Phase-locked Loop for Active Power Filtering under Distorted Grid Conditions
下载PDF
导出
摘要 电网畸变条件下,如频率脉动、电压谐波过大和存在直流分量时,会导致有源电力滤波器的锁相精度下降,为此提出了一种由滑动平均滤波器(MAF)和同步锁相环(SRF-PLL)组成的有源电力滤波器同步锁相方法,该方法在同步旋转坐标系中利用滑动平均滤波器(MAF)从畸变电网信号中提取精确的基波正序分量,保证了SRF-PLL无静差、高精度的跟踪电网的相位,从而使有源电力滤波器在电网畸变条件下具有很好的适应性,仿真和试验结果验证了该锁相方法的有效性和优越性。 The operation of active power filters under distorted grid conditions, such as grid-frequency fluctuation and voltage-harmonics and DC component, can lead to significant degradation in harmonic compensation performance. For that reason, this paper combines the moving average filter with the synchronous rotating frame phase-locked loop (SRF- PLL) to improve the performances of conventional SRF-PLL. It utilizes the moving average filter (MAF) to accurately ex- tract the fundamental positive-sequence component of grid voltage under the synchronous reference frame. The SRF-PLL achieves the accurate synchronization with zero steady state errors, so as to ensure that the active power filter has good adaptability under the condition of grid distortion. The simulation and experimental results verify the effectiveness of the superior performance.
出处 《水电能源科学》 北大核心 2018年第2期192-195,216,共5页 Water Resources and Power
关键词 电网畸变 有源电力滤波器 电能质量 滑动平均滤波器 同步锁相环 distorted grid~ active power filter~ power quality~ moving average filter~ SRF-PLL
  • 相关文献

参考文献2

二级参考文献33

  • 1成剑,罗安,付青.简化DFT滑窗迭代算法在有源电力滤波器谐波检测中应用[J].电力自动化设备,2005,25(5):57-60. 被引量:27
  • 2郭希铮,韩强,杨耕,杨公训.可选择谐波型有源电力滤波器的闭环控制和实现[J].电工技术学报,2006,21(9):51-56. 被引量:28
  • 3杨淑英,张兴,张崇巍,谢震.基于自适应谐振调节器的变速恒频风力发电双馈驱动研究[J].中国电机工程学报,2007,27(14):96-101. 被引量:12
  • 4Takeda M, Ikeda K, Tominaga Y. Harmonic current compensation with active filter[C]. IEEE Industry Apptications Society Annunal Meeting, 1987: 808-815.
  • 5Akagi H. New trends in active filters for power conditioning[J]. IEEE Transactions on Industry Applications, 1996, 32(6): 1312-1322.
  • 6Mattavelli P. A closed-loop selective harmonic compensation for active filters[J]. IEEE Transactions on Industry Applications, 2001, 37(1): 81-89.
  • 7Miret J, Castilla M, Matas J, et al. Selective harmonic-compensation control for single-phase active power filter with high harmonic rejection[J]. IEEE Transactions on Industrial Electronics, 2009, 56(8): 3117-3127.
  • 8Asiminoaei L, Blaabjerg F, Hansen S. Detection is key-Harmonic detection methods for active power filter applications[J]. IEEE Industry Applications Magazine, 2007, 13(4): 22-33.
  • 9Schauder C D, Moran S A. Mutiple reference frame controller for active filters and power line conditioners[P]. 5 309 353, 1994.
  • 10Newman M J, Zmood D N, Holmes D G. Stationary frame harmonic reference generation for active filter systems[J]. IEEE Transactions on Industry Applications, 2002, 38(6): 1591-1599.