期刊文献+

基于PCA的核电站传感器状态监测方法研究 被引量:2

Research on Condition Monitoring Technique of Sensors in NPPs Based on PCA
原文传递
导出
摘要 针对目前核电站中以物理冗余为主的传感器状态监测方法所存在的不足之处,提出了基于主元分析(PCA)的传感器状态监测方法,这种基于解析冗余的方法是对物理冗余方法的验证,解决了物理冗余方法不能实现传感器小漂移的监测,改善了冗余传感器组中多数传感器出现共模故障时,物理冗余监测方法可能给出错误融合结果的问题。使用核电站的真实传感器数据建立PCA监测模型,人为引入故障到测试数据中进行分析,仿真结果验证了文中提出的传感器状态监测模型的有效性。 To solve the shortcomings of physical redundancy methods, Principal Component Analysis (PCA) is adopted. Firstly, PCA can be used to verify the monitoring results of physical redundancy method. Secondly, PCA method can detect the small drift of sensors which physical redundancy method can hardly deal with. Finally, PCA method can detect the common mode faults in the redundant sensors. At the end of this paper, sensor measurements from a real NPP are used to train the PCA model. Artificial failures are imposed to the original measurements. Simulation results show that the PCA method has good effects on the issues that have been raised above.
出处 《核动力工程》 EI CAS CSCD 北大核心 2018年第1期136-139,共4页 Nuclear Power Engineering
基金 国家国防科技工业局项目"核动力装置在线监测与运行支持技术研究"(KY11500160001)
关键词 传感器 物理冗余 漂移 基于主元分析(PCA) 状态监测 Sensor, Physical redundancy, Drift, Principal Component Analysis (PCA) , Condition monitoring
  • 相关文献

参考文献2

二级参考文献14

  • 1马俊朋,蔡子亮.Profibus-DP现场总线技术在水电厂监控中的应用[J].仪表技术与传感器,2006(7):29-30. 被引量:11
  • 2NUREG/CR - 6343. On-Line Testing of Calibration of Process Instrumentation Channels in Nuclear Power Plants, US Nuclear Regulatory Commission 1995.
  • 3NUREG -0800. Guidance on Cross Calibration of Protection System Resistance Temperature Detectors, UNITED STATES NUCLEAR REGULATORY COMMISSION, Washington, DC, 1997.
  • 4NRC Information Notice 89 -42. Failure of Rosemont Models 1153 and 1154 Transmitters, UNITED STATES NUCLEAR REGULATORY COMMISSION, Washington, DC (1985).
  • 5HASHEMIAN H M, PETERSEN K M. Loop current step response method for in-place measurement of response time of installed RTDs and fllermocouples, Volume Six, American Institute of Physics, Toronto, (1992) 1151-1156.
  • 6NUREG/CR -5383. Effect of Ageing on Response Time of Nuclear Plant Pressure Transmitters, Analysis and Measurement Services Corporation/US Nuclear Regulatory Commission, Washington, DC (1989).
  • 7Regulatory Guide 1. 118, Rev. 2. Periodic Testing of Electric Power and Protection Systems, UNITED STATES NUCLEAR REGULATORY COMMISSION (1978).
  • 8IAEA TECDOC - 1147. Management of Ageing of I&C Equipment in NPPs, June 2000.
  • 9NUREG/CR -5501. Advanced Instrumentation and Maintenance Technologies for Nuclear Power Plants, US Nuclear Regulatory Commission ( September 1998 ).
  • 10谢志国 张秀春 王振营.岭澳二期DCS TXP部分VOTER功能优化研究.大亚湾核电,2010,(3):46-49.

共引文献6

同被引文献15

引证文献2

二级引证文献14

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部