期刊文献+

1000 kV特高压变压器调压原理及其仿真分析 被引量:7

Regulation-compensation Principle and Simulation Analysis in 1000 kV UHV Transformer
下载PDF
导出
摘要 1000 kV特高压南阳站是我国特高压交流示范工程,特高压变压器是特高压变电站内的重要设备。变电站内2台不同厂家生产的变压器分别采用完全补偿和非完全补偿的调压方式。文中介绍了2台不同原理变压器的绕组连接方式及调压原理,分别建立了调压补偿原理的Simulink仿真模型,并通过变压器电压仿真数据证实了仿真模型的正确性,最后对2台主变的中低压侧电压进行了对比分析,并根据对比结果针对特高压电网建设提出建议,以期为后期特高压建设提供参考。 1000 kV UHV Nanyang substation is a UHV AC demonstration substation engineering project in our country. The UHV transformer is an important equipment in the substation. There are two transformers, which were produced by different companies, using fully compensated and non-fully compensated regulation-compensation principle. The winding connection method and regulation-compensation principle of the two transformers are introduced. The Simulink simulation models of the two transformers are established. The simulation data of the voltage of the transformer confirms the correctness of the simulation model. Finally, some suggestions on the construction of UHV are put forward according to the comparison results, which provide reference for the construction of UHV at later stage.
作者 冯顺 曲欣 王毅 焦海龙 张军永 封永才 FENG Shun;Qu Xin;WANG Yi;ZHANG Junyong;FENG Yongcai(State Gird Henan Electric Power Corporation Maintenance Company Operation, Zhengzhou 450006, Chin)
出处 《电力工程技术》 2018年第1期109-112,121,共5页 Electric Power Engineering Technology
关键词 特高压 南阳站 调压补偿变压器 仿真分析 UHV Nanyang substation regulation-compensation transformer simulation analysis
  • 相关文献

参考文献15

二级参考文献108

共引文献151

同被引文献110

引证文献7

二级引证文献30

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部