摘要
针对一起由非全相继电器异常动作引起的跳闸事故,结合非全相,自动重合闸及防跳功能分析了整个动作过程。从机构防跳和操作箱防跳的二次回路着手,分析了两类防跳的启动条件,结果表明采用机构防跳可使系统减少1次冲击,可以提高系统的暂态稳定性,降低断路器在短时间内动作次数,延长断路器寿命。
Combining the open-phase relay,automatic reclosing and anti-bouncer functions,this paper analyzes the whole process of the trip accident caused by the abnormal action of open-phase relay. Preceding from secondary circuit of mechanism anti-bouncer and operating box anti-bouncer,this article analyzes the starting conditions of two types of anti-bouncer. The result shows that taking mechanism anti-bouncer,the power system can be reduced by one shock and improved the transient stability of the system. In condition,it will be reducing the number of operation in a short time and prolonging the life of the circuit breaker.
作者
张韶光
王煊
王晨宇
张岩坡
孙思达
渠红涛
Zhang Shaoguang;Wang Xuan;Wang Chenyu;Zhang Yanpo;Sun Sida;Qu Hongtao(State Grid Hebei Electric Power Co.Ltd.Maintenance Branch, Shijiazhuang 050071, China;Huaneng International Electric Power Co.Ltd. Shang'an Plant, Shijiazhuang 050310, China)