摘要 通过中试实验研究了三级组合生物滤池强化脱氮效果,考察了第二级好氧滤柱回流比对工艺前置反硝化的影响,第三级滤池外加碳氮比对后置反硝化强化脱氮效果的影响。结果表明,在进水流量为0.5 m^3/h,水温为18℃左右,第二级好氧滤柱气水比为3:1时,在回流比为100%时,前置反硝化脱氮能达最佳效果,TN去除率为54.07%,出水TN浓度平均值为19.94 mg/L,不同回流比下,COD、NH_4^+-N均有较高去除率。为进行强化脱氮,在第三级缺氧滤柱前投加碳源,碳氮比为7:1时,第三级对TN去除率为40.7%,出水TN平均值为11.84 mg/L。三级组合生物滤池结合前置和后置反硝化工艺对TN有很好的去除效果,稳定运行后,系统对TN平均去除率达到72.96%。 The effect of nitrogen removal by three stage combined biofilter was studied in pilot scale, test the influence of the reflux ratio of second stage aerobic filter column on pre-denitrification, and test the influence of the C/N ratio of third stage filter on post-denitrification. The result show that when the influent flow was 0.5 m3/h,the water temperature was about 18 ℃, the average value of TN concentration was 19.94 mg/L. Under different reflux ratio, COD and ammonia nitrogen had high removal rate. In order to enhance the removal of nitrogen, the test added carbon source before the third stage anoxic filter column. When C/N ratio was 7, the TN removal rate of third stage was 40.7%,the average effluent value of TN was 11.84 mg/L. Three stage combined biological filter combined pre and post denitrification process, had a good removal effect on TN, the average removal rate of TN was achieved 72.96%.
作者 徐姮 陆少鸣 李嘉树 江荻 端艳 XU Heng;LU Shaoming;LI Jiashu;JIANG Di;DUAN Yan(College of Environment and Energy,South China University of Teehnology, Guangzhou 510006,China)
出处 《水处理技术》 CAS CSCD 北大核心 2018年第5期84-87,102,共5页 Technology of Water Treatment
基金 国家重点研发计划项目(2016YFC0400705)
关键词 组合生物滤池 回流比 碳氮比 反硝化作用 combined biofilter reflux ratio C/N denitrification
  • 相关文献

参考文献1

二级参考文献15

  • 1祁佩时,李渊博,刘云芝,夏晓寒.前置反硝化二段BAF深度处理中药废水试验研究[J].中国给水排水,2006,22(z1):267-270. 被引量:3
  • 2邱立平,马军.曝气生物滤池的生物膜及其微生物种群特征[J].中国环境科学,2005,25(2):214-217. 被引量:48
  • 3Chen J J, Mccarty D, Slack D. 2004. Full scale studies of a simplified aerated filter(BAF) for organic and a nitrogen removal [ J]. Water Science and Technology, 41 (4) : 1-4.
  • 4Collins A, Clarkson W, Vrona M. 2006. Fixed-film biological nitrification of a strong industrial waste [J]. Journal of Water Pollution Control Federation, 60 (4) : 499-504.
  • 5Fdz-Polanco F, Mendez E, Uruena A, et al. 2004. Spatial distribution of heterotrophs and nitriers in a submerged biofilter for nitrification [ J]. Water Research, 34(10) : 4081-4089.
  • 6Hong-Duek R, Daekeun D, Heun K, et al. 2008. Nitrogen removal of low carbon/nitrogen wastewater with four-stage biological aerated filter system [ J]. Process Biochemistry, 43 (7) : 729-735.
  • 7Lacalle M, V' dlaverde S, Fdz-polanco F, et al. 2001. Combined anaerobic/aerobic system for organic matter and nitrogen removal from a high strength industrial wastewater [ J]. Water Science and Technology, 44(4) : 255-262.
  • 8Pujol R. 2002. Process improvements for upflow submerged biofilters [J]. Water Science and Technology, 32( 1 ) : 25-29.
  • 9Pujol R, Tarallo S. 2004. Total nitrogen removal in two-step biofiltration [J]. Water Science and Technology, 41 (4-5) : 65-68.
  • 10Puzava N, Payraudeau M, Thornber D. 2005. Simultaneous nitrification and denitrification in biofiters with real time aeration control [ J]. Water Science and Technology, 43 ( 1 ) : 269-276.

共引文献32

同被引文献58

引证文献8

二级引证文献25

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部