摘要
介绍了无锡宜家购物中心因租户配电母线槽发生相间短路导致10 k V母线进线开关越级跳闸,从而引起购物中心大面积停电事故。描述了寻找故障的过程和采取应急措施的方法,以及事后对事故现场进行勘查,对故障原因进行分析,邀请开关柜制造商到现场对故障系统检测后制定了一套电气故障防范措施,可为类似购物中心的电气设计及电气设备调试和日后的运营维护提供参考。
The large-scale power supply blackout accident of IKEA shopping mall was introduced,which attributed the override trip of 10kV bus feeder switch for the interphase short circuit of tenant distribution bus duct. The process of finding fault and the methods of emergency measures were described. After the accident investigation,the causes of faults were analyzed. After switchgear manufacturer tested the fault system on the scene,the protective measures for electrical faults were established. It can provide references for electrical design,electrical equipment commissioning and future operation and maintenance of similar shopping malls.
作者
居帼强
JU Guoqiang(IKEA Centres(China) Co., Ltd., Shanghai 200235, Chin)
出处
《现代建筑电气》
2018年第4期39-44,共6页
Modern Architecture Electric
关键词
购物中心
预防措施
继电保护整定
选择性保护
shopping mall
prevention measures
protective relaying setting
selective protection