期刊文献+

长沙某商业建筑空气-空气能量回收装置节能性分析

Energy Saving Analysis of Air-to-air Energy Recovery Equipment in a Commercial Building in Changsha
下载PDF
导出
摘要 通过对长沙市典型气象年逐时气象参数、商业建筑供冷和供热工况下新风逐时送风温差和送风焓差进行分析,分别得出采用显热型和全热型空气-空气能量回收装置的逐时回收能量。结果表明,长沙市夏季高温高湿气候条件下,加之冬季制热工况下节约的能量,采用全热回收装置节能量显著,具有较好的经济效益,投资回收期约4.4年。 The hourly air supply temperature difference and enthalpy difference of fresh air are analyzed,based on the hourly parameters of typical meteorological year in Changsha,and cooling and heating conditions of a commercial building. Respectively,the hourly recovered energy is obtained by sensible-heat and full-heat air-to-air energy recovery equipment. The results show that,under the high temperature and high humidity conditions in summer of Changsha,with the energy saving under heating conditions in winter,the air-to-air energy recovery equipment saves energy significantly with good economic benefits,and its investment recovery period is about 4. 4 years.
作者 张勇华 ZHANG Yong-hua(China Machinery International Engineering Design and Research Institute Co. , Ltd. , Changsha 410007, China)
出处 《建筑节能》 CAS 2018年第5期108-111,共4页 BUILDING ENERGY EFFICIENCY
关键词 空气-空气能量回收装置 全热回收装置 显热回收装置 长沙 商业建筑 air - to - air energy recovery equipment total heat exchange equipment sensible heatexchange equipment Changsha commercial building
  • 相关文献

二级参考文献5

  • 1中国建筑科学研究院.GB/T21087-2007空气-空气能量回收装置[S].北京:中国标准出版社,2008
  • 2中国气象局,清华大学.中国建筑热环境分析专用气象数据集[M].北京:中国建筑工业出版社,2005.
  • 3中国建筑科学研究院,中国建筑业协会建筑节能专业委员会.GB50189-2005公共建筑节能设计标准[S].北京:中国建筑工业出版社,2005
  • 4国家发展和改革委员会能源研究所.GB2589-2008综合能耗计算通则[S].北京:中国标准出版社,2008.
  • 5中国建筑科学研究院.可再生能源建筑应用示范项目测评导则[G].2008.