摘要
半波长线路的输电距离远,电气特征与现有特高压线路存在较大差异。由于线路沿线电压最大值位置在线路中间,常规的过电压保护无法满足半波长线路的要求。本文对半波长线路稳态运行电压特性做了深入的分析,研究了半波长线路稳态运行过电压的影响因素,并推导出了线路沿线电压最大值位置与线路功率传输的关系。在此基础上,提出了一种适用于半波长线路的过电压保护方法。EMTP仿真表明,该方法可以准确计算出沿线电压最大值,并保护线路全长。
The transmission distance of half-wavelength lines is comparatively longer,therefore,their electrical charac?teristics are obviously different from those on the existing high-voltage transmission lines.As the position of the maxi?mum voltage locates in the middle of transmission lines,the conventional over-voltage protection cannot satisfy the re?quirement of half-wavelength lines.In this paper,the steady-state voltage characteristics of half-wavelength lines are ana?lyzed in depth,and the influencing factors of over-voltage of half-wavelength lines under steady-state operation are stud?ied.In addition,the relationship between the maximum voltage position and line transmission power is deduced.On this basis,an overvoltage protection method for half-wavelength lines is proposed. EMTP simulations show that this method can accurately calculate the maximum voltage along the transmission line and protect the full length of the line .
作者
赵青春
谢华
郭子煊
李斌
朱晓彤
ZHAO Qingchun;XIE Hua;GUO Zixuan;LIBin;ZHU Xiaotong(NR Electric Co.,Ltd,Nanjing 211102,China;Key Laboratory of Smart Grid of Ministry of Education,Tianjin University,Tianjin 300072,China)
出处
《电力系统及其自动化学报》
CSCD
北大核心
2018年第5期63-68,共6页
Proceedings of the CSU-EPSA
基金
国家电网公司科技资助项目(31966)
关键词
半波长输电线路
稳态
过电压
继电保护
half-wavelength transmission line;steady-state;overvoltage;relay protection