含逆变型分布式电源配电网的接地故障中性点电压分析及对策 被引量:6

Analysis on Neutral Point Overvoltage during Grounded Fault in Distribution Network with Inverter-interfaced DGs and Countermeasures
原文传递
导出
摘要 大量逆变型分布式发电(distributed generator,DG)接入导致变压器中性点过电压甚至间隙击穿等事故发生,研究中性点过电压的分析计算以及保护配置迫在眉睫。文章采用序分量理论,推导并简化了故障发生后开关跳开前后变压器中性点过电压理论计算公式。该公式形式简单、计算结果准确,可以广泛应用于规划运行分析中。根据计算公式,分析出了影响过电压的主要因素并提出了保护配置方法。PSCAD仿真算例验证了计算公式的正确性,并讨论了DG输出限流等因素对过电压的影响。 Injection of a large number of inverter-interfaced distributed generators(DGs) has led to neutral point overvoltage and even caused vacuum breakdown,which makes it imminent to analyze neutral point overvoltage in detail,as well as to concern the protection configuration there. In this paper,sequence component theory is used to derivate and simplify theoretical calculation formulas of neutral point overvoltage before and after trip during fault,which is very simple and accurate and can be widely used in system planning and operation. On the basis of these formulas,main factors influencing overvoltage are analyzed and related protection configuration is proposed. Correctness of the formulas is verified by simulation in PSCAD,and the influencing factors of overvoltage such as output current of DGs are analyzed.
作者 姜淼 徐光福 李正红 魏承志 陈俊 JIANG Miao;XU Guangfu;LI Zhenghong;WEI Chengzhi;CHEN Jun(NR Electric Co. , Ltd. , Nanjing 211102, China;China Southern Power Grid Company Limited, Guangzhou 510080, China)
出处 《电力建设》 北大核心 2018年第5期70-76,共7页 Electric Power Construction
基金 南方电网重点科技项目(ZDKJQQ2015012)~~
关键词 分布式电源 单相接地故障 序分量 中性点过电压 DG phase to earth fault sequence component neutral point overvoltage
  • 相关文献

参考文献13

二级参考文献191

共引文献1434

同被引文献83

引证文献6

二级引证文献32

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部