期刊文献+

回热器对新型混合制冷剂热泵循环性能影响的实验研究 被引量:1

Experimental study on the effect of the regenerator on the performance of a new type mixed refrigerant of heat pump cycle
原文传递
导出
摘要 以新型混合制冷剂(质量百分比91.83%的R218和8.17%的R846)为实验工质,在板式回热器热泵系统中进行实验,分析实验装置中回热器对热泵循环性能的影响。结果表明,回热器用板式替代套管式后,回热器进出口温差从10℃增加到26℃,回热效果明显,系统性能得到改善。进一步分析回热量对系统性能的影响,得出随着回热量的增加,压缩机耗功增加30.3%,但系统制热量增加85.5%,制热系数增加41.7%,系统性能显著提高。 A new mixed refrigerant (mass percentage of 91.83% for R218 and 8.17% for R846) was proposed as an ex- perimental refrigerant in a plate regenerator heat pump system. The influence of the regenerator on the performance of heat pump cycle was analyzed. The results show that the temperature difference between the inlet and the outlet of the regenerator increases from 10℃ to 26 ℃ after the type of regenerator is replaced tubular by the plate type. It means the heat recovery effect is obvious and the system performance is improved. Further analysis of the impact of heat recovery on system performance shows that with the increase of heat recovery amount, work consumption of compressor increases by 30.3%, but the heating capacity of the sys- tem increases by 85.5% , the coefficient of heating increases by 41.7% and the performance is significantly improved.
作者 额热艾汗 汪秋刚 李靖 任玉成 王昭阳 赵纯 李俊峰 Ereaihan;Wang Qiugang;Li Jing;Ren Yucheng;Wang Zhaoyang;Zhao Chun;Li Junfeng(College of Water Conservancy and Architecture Engineering, Shihezi University, Shihezi 832002, China;Key laboratory of the Three Gorges Reservoir Region' s Eco - Environment, Ministry of Education, Chongqing University, Chongqing 400045, China;The National Centre for International Research of Low - Carbon and Green Buildings, Chongqing University, Chongqing 400045, China)
出处 《低温与超导》 CAS 北大核心 2018年第6期66-70,共5页 Cryogenics and Superconductivity
基金 新疆生产建设兵团应用基础研究计划(2016AG003) 石河子大学高层次人才科研启动项目(RCZX2015027 RCZX2015028) 石河子大学自主项目(ZZZC201605)资助
关键词 回热器 混合制冷剂 热泵 循环性能 制热系数 Regenerator Mixed refrigerant Heat pump Cyclic performance Coefficient of heating
  • 相关文献

参考文献4

二级参考文献71

  • 1王鹏英,徐琨,秦雯.新工质R125热力性质图表研制[J].上海工程技术大学学报,2001,15(2):88-93. 被引量:2
  • 2向立平,曹小林,席占利,欧阳琴.回热器对制冷循环性能影响的研究[J].制冷与空调(四川),2005,19(4):38-42. 被引量:19
  • 3李洪芳.R142b、R152a等64种工质的热力性质的计算[J].上海水产大学学报,1996,5(2):83-89. 被引量:6
  • 4Domanski P A, Didion D A. Thermodynamic evaluation of R22 alternative refrigerants and refrigerant mixtures [ J ] ASHRAE Transactions, 1993,99 (2) : 636 - 48.
  • 5Domanski P A, Didion D A, Doyle J P. Evaluation of suction - line / liquid - line heat exchange in the refrigeration cycle[J]. Rev. Int. Froid. , 1994,7(7) :487 -93.
  • 6Klein S A,Reindl D T, Brownell K. Refrigeration system performance using liquid - suction heat exchangers [ J ]. Intemation Journal of Refrigeration, 2000,23:588 - 596.
  • 7张永钢 吴宣中.基于R404A的小型冷风机的实验研究.制冷学报,2002,.
  • 8Man-Hoe Kim,Jostein Pettersen,Clark W Bullard.Fundamental process and system design issues in CO2 vapor compression systems[J].Progress in Energy and Combustion Science,2004,30:119-174.
  • 9Kays W M,London A L.Compact Heat Exchangers[M].New York,McGraw-Hill Book Company,1984.
  • 10Seok Ho Yoon,Ju Hyok Kim,Yun Wook Hwang,et al.Heat transfer and pressure drop characteristics during the in-tube process of carbon dioxide in the supercritical region[J].International Journal of Refrigeration,2003,26:857-864.