期刊文献+

考虑地线电晕影响的雷击输电线路杆塔的时域有限差分分析

Analysis on Lightning Transmission Towers with Ground Corona Based on FDTD
下载PDF
导出
摘要 对雷击输电线路的研究是保障线路安全、稳定运行的重要措施。采用时域有限差分(FDTD)方法,在考虑地线产生电晕的条件下,对雷电反击输电线路杆塔进行仿真分析。仿真中采用了一个简化的电晕放电模型,分别考虑反击闪络发生在上、中、下三相导线上,对输电线路暂态过电压进行了计算分析。仿真结果表明,地线电晕可以降低雷击时杆塔的暂态电压幅值,并且增加闪络发生的时间。 The study on back-flashover at transmission line tower is important to assure the stable working of transmission lines.The back-flashover at transmission towers struck by lightning in the presence of corona emanated at the ground wire is simulated with finite-difference time-domain method.A simplified model of corona discharge is applied,and the counterattack flashover on the upper, middle and lower wires are considering,the transient overvohage of transmission lines are analyzed.The simulation results show that the ground wire corona can reduce the transient voltage amplitude of the lines and increase the duration of flashover.
作者 刘三伟 王峰 张柳 王成 LIU Sanwei;WANG Feng;ZHANG Liu;WANG Cheng(State Grid Hunan Electric Power Corporation Research Institute, Changsha 410007, China)
出处 《山东电力技术》 2018年第5期19-23,共5页 Shandong Electric Power
关键词 雷电反击 电晕放电 时域有限差分方法 暂态过电压 back-flashover corona discharge finite-difference time-domain method transient overvoltage
  • 相关文献

参考文献3

二级参考文献31

  • 1莫付江,陈允平,阮江军.输电线路杆塔模型与防雷性能计算研究[J].电网技术,2004,28(21):80-84. 被引量:119
  • 2莫付江,陈允平,阮江军.架空输电线路雷击感应过电压耦合机理及计算方法分析[J].电网技术,2005,29(6):72-77. 被引量:45
  • 3Lundholm R. Overvoltage in a direct lightning-stroke to a transmission-line tower[R]. CIGRE Session ,1958
  • 4Lundholm R, Finn R B, Price W S. Calculation of transmission line lightning voltages by field concepts[J].AIEE, Part Ⅲ, 1958: 1271-1283
  • 5Wagner C F, Hileman A R. A new approach to calculation of lightning performance of transmission lines-Ⅱ[J]. AIEE, Part Ⅲ, December,1959:996-1020
  • 6Wagner C F, Hileman A R. A new approach to the calculation of the lightning performance of transmission lines-Ⅲ[J]. AIEE, Part Ⅲ, October, 1960: 589-603
  • 7Goni M O, Cheng P T, Takahashi H. Theoretical and Experimental Investigations of the Surge Response of a Vertical Conductor [C]// Transmission and Distribution Conference and Exhibition 2002. Asia Pacific. IEEE/pes. 20022(10): 699-704
  • 8Chowdhuri P, Li S, Yah P, Rigorous Analysis of Back-flashover Outages Caused by Direct Lightning Strokes to Overhead Power Line [J]. IEE Proc-gener. Transm. Distrib.2002, 149(1): 58-65.
  • 9Shoory A, Moini R, Sadeghi S H H. Analysis of Lightning Electromagnetic Fields in the Vicinity of a Lossy Ground,Using a New Antenna Theory Model [C]// Power Tech Conference Proceedings, 2003 IEEE Bologna, 2003, 1 (6):23-26.
  • 10IEEE Working Group Report. Estimating Lightning Performance of Transmission Lines Ⅱ, Updates to Analytical Models[J].IEEE Trans. on Power Delivery, 1993, 8(3):1 254-1 267.