介绍一起电网运行中零序过压保护动作造成变压器动作跳闸的真实案例。以故障录波信息为依据,结合实际情况,分析继电保护装置动作过程,从变电运维角度阐述此类故障特征,从而避免相同类型故障的发生。
A real case of the transformer protection caused by zero-sequence over-voltage protection action in the operation of the power grid was introduced. Based on the fault recording information and the actual situation,the operation of the relay protection device was analyzed. The characteristics of this kind of fault were described from the angle of substation operation and maintenance,so as to avoid the occurrence of the same type of fault.