本文分析保护动作时刻故障录波,判断出选相合闸装置未能正确控制合闸的初相角是导致励磁涌流过大原因,并对保护装置在本次故障中的动作行为进行评价。
This paper analyzes the fault recording of the protection action time and judges that the primary phase angle of the phase selection switching device being not properly controlled is the cause of excessive magnetizing inrush current,Tt also evaluates the action of the protection device in this fault.
作者
张宇
杨洁民
ZHANG Yu;YANG Jiemin(Tianshengqiao Bureau of EHV Transmission Company , China Southern Power Grid Co. , Ltd. , Xingyi 562400 , Chin)
出处
《电工技术》
2018年第10期43-44,46,共3页
Electric Engineering
关键词
变压器空充
励磁涌流
选相合闸
交流滤波器
charging of no-load transformer
magnetizing inrush current
phase selection switching
AC filter