摘要 本文分析保护动作时刻故障录波,判断出选相合闸装置未能正确控制合闸的初相角是导致励磁涌流过大原因,并对保护装置在本次故障中的动作行为进行评价。 This paper analyzes the fault recording of the protection action time and judges that the primary phase angle of the phase selection switching device being not properly controlled is the cause of excessive magnetizing inrush current,Tt also evaluates the action of the protection device in this fault.
作者 张宇 杨洁民 ZHANG Yu;YANG Jiemin(Tianshengqiao Bureau of EHV Transmission Company , China Southern Power Grid Co. , Ltd. , Xingyi 562400 , Chin)
出处 《电工技术》 2018年第10期43-44,46,共3页 Electric Engineering
关键词 变压器空充 励磁涌流 选相合闸 交流滤波器 charging of no-load transformer magnetizing inrush current phase selection switching AC filter
  • 相关文献

参考文献1

二级参考文献2

  • 1H John, Brunke, J Klaus, et al. Elimination of Transformer Inrush Current by Controlled Switching-partI :Theoretical Consideration [J]. IEEE T Power Deliver, APR 2001, 16(2):276-280.
  • 2H John, Brunke, J Klaus, et al. Elimination of Transformer Inrush Current by Controlled Switching-PartⅡ: Application and Performance Considerations[J]. IEEE Power Deliver, APR 2001, 16(2): 281-285.