摘要 复合绝缘子断串问题是威胁输电线路安全稳定运行的关键问题。为系统分析复合绝缘子断串类型和原因,文中对实际运行复合绝缘子断串样品进行了统计分析,并对金具破损及芯棒脆断等引起的断串问题进行了总结归纳。结果表明绝缘子芯棒断串原因主要为端部密封失效、外护套破损、芯棒与护套界面粘结失效等。基于上述分析,文中提出了加强入网检测和运行性能分析、重视日常带电检测工作及对重要通道复合绝缘子技术改造三方面措施,从而为复合绝缘子断串防治提供参考。 The fracture problems of the composite insulators are the key problems to threat the security and stability of thetransmission line. In order to analyze the types and causes of the fracture problem,this paper studies the fracture samples of thecomposite insulators and classifies the fracture types of insulator hardware and FRP rod. Studied shows that the causes includedthe invalidation of sealant,breakage of the sheath and splice failure between the FRP rod and the sheath. To solve theproblems,three solutions including performance test,on line detection and technical transformation of the composite insulatorsin the important passage are proposed. And preventing suggestions to the fracture problems are provided.
作者 李鸿泽 LI Hongze(State Grid Jiangsu Electric Power Co.,Ltd.,Nanjing 210024,China)
出处 《电力工程技术》 2018年第4期51-56,共6页 Electric Power Engineering Technology
基金 国家自然科学基金资助项目(51377093)
关键词 复合绝缘子 断串 金具 芯棒 带电检测 composite insulators fracture problem insulator hardware FRP rod online detection