期刊文献+

252 kV GIS局部放电试验仿真平台设计研究

Study on 252 kV GIS Partial Discharge Test Simulation Platform Design
下载PDF
导出
摘要 GIS(Gas Insulated Switchgear)内部由于绝缘缺陷导致局部放电,严重损害内部器件的绝缘性能,需采取一定的手段和方式对局部放电进行检测。结合国内GIS局部放电的研究成果,综合各种检测方法和电子设计方案,对252 kV GIS局部放电仿真平台进行设计和试验演示。结果证明:该仿真平台设计能够很好地模拟典型的绝缘缺陷以及局部放电过程,同时能够为试验观察和检测提供便捷条件。 GIS (Gas Insulated Switchgear) is a closed type gas insulated switchgear which is widely used in power system because of its small size, strong anti-interference ability and reliability. However, due to its internal insulation defects caused by partial discharge (PD) phenomenon,it seriously damage the insulation performance of the device.It must take a certain means and methods for the detection of partial discharge.The research results of GIS partial discharge in China combined with various detection methods and electronic design, analyzing and completing the design of 252 kV GIS partial discharge simulation platform.The experimental demonstration and the results show that the simulation platform can simulate the typical insulation defects.The partial discharge process can provide convenient conditions for the experimental observation,detection and can achieve the purpose of the platform design.
作者 杜彦强 毕海涛 师政 冯占稳 黄福存 DU Yanqiang;BI Haitao;SHI Zheng;FENG Zhanwen;HUANG Fucun(Electric Power Research Institute of State Grid Liaoning Electric Power Co.,Ltd.,Shenyang,Liaoning 110006,China)
出处 《东北电力技术》 2018年第6期13-15,共3页 Northeast Electric Power Technology
关键词 GIS局部放电 试验平台设计 绝缘缺陷 GIS partial discharge;test platform design;insulation detect
  • 相关文献

参考文献2

二级参考文献26

  • 1钱勇,黄成军,江秀臣,肖燕.基于超高频法的GIS局部放电在线监测研究现状及展望[J].电网技术,2005,29(1):40-43. 被引量:165
  • 2孙才新,许高峰,唐炬,陆宠惠,侍海军.以盒维数和信息维数为识别特征量的GIS局部放电模式识别方法[J].中国电机工程学报,2005,25(3):100-104. 被引量:62
  • 3程养春,李成榕,王伟.局部放电检测中傅立叶级数法与几种抗干扰方法的比较分析[J].电网技术,2005,29(12):33-38. 被引量:8
  • 4王昌长 李福琪.电力设备的在线监测与故障诊断[M].北京:清华大学出版社,1996..
  • 5IEC 60270,Highvoltage test techniques:partial discharge measurements[S].
  • 6CIGRE WG 15.03.Diagnostic methods for GIS insulating systems[C].CIGRE,Paris,1992:15/23-01.
  • 7Hampton B F,Meats R J.Diagnostic measurements at UHF in gas insulated substations[J].IEEProceedings,1988,135(2):137-145.
  • 8Judd M D,Farish O.Transfer functions for UHF partial discharge signals in GIS[C].Eleventh International Symposium on High Voltage Engineering,London,1999,5:74-77.
  • 9JuddMD,FarishO,HamptonBF,The excitation of UHF signals by partial discharges in GIS[J].IEEE Trans on Dielectrics and Electrical Insulation,1996,3(2):213-228.
  • 10BOLIN P,KOCH H. Introduction and applications of gas insulated substation (GIS) [C]//IEEE Power Engineering Society General Meeting 2005. San Francisco, California, United States : IEEE, 2005 : 920-926.