期刊文献+

考虑不对称故障影响的多馈入直流系统换相失败快速判别方法 被引量:16

Fast Detection Method of Commutation Failure in Multi Infeed DC System Considering the Effect of Unbalanced Fault
下载PDF
导出
摘要 多直流馈入系统中直流输电的动态特性对系统整体稳定性的影响成为突出问题。提高交流系统不对称故障时直流准稳态模型对换相失败情况识别的准确度,对于提高系统分析精度具有重要意义。该文从逆变器换流阀的换流方程出发,考虑不对称故障时负序电压分量对换相电压角度偏移的影响,提出一种换相失败风险的快速识别判据。该判据在目前的高压直流准稳态模型基础上稍加修改即可实现。通过与机电–电磁混合仿真结果的比较,验证了文中方法的准确性与有效性。 The dynamic characteristics of HVDC transmission have a serious impact on the overall power system stability, and that has become the most severe challenge in the multi infeed DC system. The correct identification of commutation failure when unbalanced faults occurred in AC system is of great significance, especially in the stability transient simulation with a quasi steady state DC model. This paper proposed a fast identification criterion to access commutation failure risk, based on the commutation equation of inverter valve, considering the effect of negative sequence voltage components on commutation voltage angle offset during unbalanced fault. The criterion can easily be used in the current HVDC quasi steady state model. The accuracy and effectiveness of the proposed method were verified by comparison withthe results of electromechanical and electromagnetic hybrid simulation.
作者 张彦涛 邱丽萍 施浩波 韩奕 李新年 姜懿郎 ZHANG Yantao;QIU Liping;SHI Haobo;HAN Yi;LI Xinnian;JIANG Yilang(State Key Laboratory of Power Grid Safety and Energy Conservation(China Electric Power Research Institute),Haidian District,Beijing 100192,China)
出处 《中国电机工程学报》 EI CSCD 北大核心 2018年第16期4759-4767,共9页 Proceedings of the CSEE
基金 国家电网公司科技项目(XT71-15-053)~~
关键词 高压直流输电 换相失败 机电暂态 负序电压分量 不对称故障 机电–电磁混合仿真 HVDC commutation failure electro-mechanical transient negative sequence voltage unbalancedfault electromechanical and electromagnetic transient hybridsimulation
  • 相关文献

参考文献26

二级参考文献300

共引文献840

同被引文献241

引证文献16

二级引证文献106

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部