摘要
介绍了泵站电力系统的二次电压回路,共性上二次电压的回路结构都可以分解为源头、母线、分支和隔离保护设备,并给出了造成二次电压回路个性的原因。通过对仙人大港泵站双向运行泵站中的二次电压回路的分析,检查出电压互感器V-V连接方式接地线接错的问题,排除了熔断高压熔丝的隐患。
Introduction was made to the secondary voltage circuit of power system in the pumping station. The secondary voltage circuit structure from the corner of generality could be divided into source, bus bar, branch and insulation blocking equipment, and the cause of secondary voltage circuitindividuality was given. After the analysis of the secondary voltage circuit of two-way running pump station in Xiaren grand port pump station, the voltage transformer was examined and it was found that the V-Vconnection with grounding wire was wrong, which eliminates the hidden danger of the high pressure fuse.
作者
张立坚
项德银
任杰
ZHANG Li-jian;XIANG De-yin;REN Jie(General Irrigation Canal Management Department of Jiangsu Province,Huaian 223212,China)
出处
《电工电气》
2018年第10期46-48,共3页
Electrotechnics Electric
关键词
二次电压回路
故障排除
双向运行泵站
secondary voltage circuit
troubleshooting
two-way running pump station