溧阳抽水蓄能电站发电机同期故障分析及处理 被引量:1

Analysis and Treatment of Synchronous Fault of Generator in Liyang Pumped-storage Power Station
下载PDF
导出
摘要 在介绍SJ-12D手自动准同期装置的工作原理的基础上,对溧阳抽水蓄能电站机组运行过程中出现的2次同期合闸失败案例进行了深入分析,对同期装置进行了改造,将同步检查继电器更换为DSLD1130数字式同步检查继电器,并对机组水头传感器定期检查排气,提高了机组同期合闸成功率。 On the basis of the understanding of operating principles of SJ-12D manual/automatic quasi-synchronization device, two failure cases of synchronous operation in Liyang Pumped-storage Power Station are analyzed. Based on the results, the synchronization device is modified. The synchronous check relay is replaced by a DSLD1130 digital synchronous check relay, and the water head sensor of unit is periodically checked for gas exhausting, which improves the success rate of simultaneous closing.
作者 许涛 宋明亮 于中舒 XU Tao;SONG Mingliang;YU Zhongshu(Jiangsu Guoxin Liyang Pumped Storage Power Generating Co.,Ltd.,Liyang 213334,Jiangsu,China)
出处 《水力发电》 北大核心 2018年第10期62-64,共3页 Water Power
关键词 发电机 同期装置 故障分析 溧阳抽水蓄能电站 generator synchronization device fault analysis Liyang Pumped-storage Power Station