基于主动注入信号法的单相接地故障定位方法 被引量:8

Single-phase Grounding Fault Location Method Based on Active Signal Injection Method
下载PDF
导出
摘要 提出了一种基于主动注入信号法的单相接地故障定位方法,当配电线路发生单相接地故障时,主动信号发生器向系统注入信号,故障指示器通过信号提取算法,提取出系统上被注入的区别于故障回路外的明显特征信号,判断出该信号后上报故障从而实现故障定位。 This paper proposes a fault location method of single-phase grounding based on active signal injection method.When a single-phase grounding fault occurs in the distribution line,the active signal generator injects signals into the system.With signal extraction algorithm,the fault indicator extracts the obvious characteristic signals that are injected into the system and different from those outside the fault loop,to determine the signals and then report the fault,so as to realize fault location.
作者 鲍小峰 肖开伟 杨隽 邵武 田庆生 李邦源 乔连留 BAO Xiaofeng;XIAO Kaiwei;YANG Jun;SHAO Wu;TIAN Qingsheng;LI Bangyuan;QIAO Lianliu(Yuxi Power Supply Bureau,Yunnan Power Grid Co.,Ltd.,Yuxi 653100,China;Postgraduate Workstation of Yunnan Power Grid Company,Kunming 650217,China;Yunnan Eleclric Test&Research Institute Group Co.,Lid.,Kunming 650217,China)
出处 《电工技术》 2018年第17期135-137,共3页 Electric Engineering
基金 南方电网公司项目(编号YNKJ00000225)
关键词 注入信号法 故障定位算法 故障指示器 特征信号提取 signal injection method fault location algorithm fault indicator characteristic signal extraction