国产阀冷系统数据处理方法及回路优化方案

Data Processing Method and Circuit Optimization Scheme of Domestic Valve Cooling System
下载PDF
导出
摘要 侨乡换流站国产阀冷系统保护和控制功能主要通过基于Simatic S7-400语言的源程序实现,为了研究其数据处理方法,着重分析高位水箱液位超低保护跳闸逻辑、模拟量高(低)和超高(超低)告警判断逻辑、模拟量数据显示判断逻辑。研究结果表明,多传感器的"三取二"、"二取二(二取一)"、"一取一"策略可规避传感器故障导致的跳闸风险,可靠性更高。同时,针对阀冷系统水回路存在的隐患问题提出了优化方案。 In Qiaoxiang converter station,the protection and control functions of domestic valve cooling system are achieved by the source program based on Simatic S7-400.In order to research the data processing method,this paper mainly analyzes the ultra-low liquid level tripping protection logic of high level cistern,judgment logic of high(low)or ultrahigh(ultra-low)analog quantity warning,judgment logic of analog quantity data display.The result shows that the two out of three,two out of two(one out of two)and one out of one strategies of multi-sensors can avoid the tripping risk caused by sensor fault and has higher reliability.Meanwhile,in view of the hidden dangers in valve cooling water loop,an optimization scheme is put forward.
作者 李金安 周登波 何园峰 LI Jin'an;ZHOU Dengbo;HE Yuanfeng(CSG EHV Power Transmission Company,GuangZhou Branch,GuangZhou 510663,China)
出处 《电工技术》 2018年第17期138-141,共4页 Electric Engineering
关键词 特高压直流 阀冷系统 冗余传感器 电导率 “三取二”逻辑 UHVDC valve cooling system redundant sensor conductivity two out three logic