期刊文献+

500kV输电线路复合绝缘子断裂事故分析 被引量:6

Analysis of Fracture Accident of Composite Insulator for 500kV Transmission Line
下载PDF
导出
摘要 本文以湖南某500kV线路复合绝缘子断裂事故为例,描述了复合绝缘子护套破损、芯棒蚀损的形貌特征,并对造成故障的可能原因进行了分析。结合运行经验及试验论证,认为端部缺陷是导致该复合绝缘子断裂的主要原因,并对复合绝缘子的运行维护等工作阶段提出了建议。 In this paper, a fracture accident of a 500 kV line composite insulator in Hunan is taken as an example to describe the topography characteristics of sheath damage and mandrel erosion of composite insulator, and the possible causes of failure are analyzed. Combining with the experience and experimental study, it is concluded that the end defect is the main reason leading to the fracture of the composite insulators. It puts forward some suggestions on the operation and maintenance working stages of composite insulators.
作者 张柳 巢亚锋 王成 岳一石 ZHANG Liu;CHAO Yafeng;WANG Cheng;YUE Yishi(State Grid Hunan Electric Power Company Limited Research Institute,Changsha 410007;Hunan Xiangdian Test Research Institute Co.,Ltd.,Changsha 410004,China)
出处 《湖南电力》 2018年第5期27-31,共5页 Hunan Electric Power
关键词 复合绝缘子 电蚀 断裂 绝缘子掉串 composite insulator electric erosion fracture insulator string broken