摘要
此文介绍了红外热像检测中,某110 kV油浸式电流互感器顶部膨胀器外壳因材质辐射率影响的案例,分析了不同金属材质影响下的红外测温结果,并提出了相应处理的措施。
This paper has introduced a typical case,of which the top extender shell of a 110 kV oil immersed current transformer is influenced by material emissivity when giver test of infrared thermography. Also analyzed is infrared temperature measured result under the influence of different metals. And measures to prevent erroneous .judgment are proposed.
作者
高微
刘晓康
闫佳文
刘哲
刘连升
GAO Wei;LIU Xiaokang;YAN Jiawen;LIU Zhe;LIU Liansheng(State Grid Hengshui Power Supply Company,Hengshui 053000,China;State Grid Hebei Electric Power Co.,Ltd.,Training Center,Shidiazhuang 050000,China)
出处
《国网技术学院学报》
2018年第5期48-50,共3页
Journal of State Grid Technology College
关键词
电流互感器
辐射率
红外测温
金属检测
current transformer
emissivity
infrared temperature measurement